Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: EVANS LINE CONSTRUCTION, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of EVANS LINE CONSTRUCTION, INC. in TEN ROD ROAD AND CAPITOL CIRCLE, ROCHESTER, NH 03839 (NAICS 237130). OSHA activity number 345505952.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Evans Line Construction, INC. — free Get an email when a new federal OSHA severe-injury report for Evans Line Construction, INC. is published. One employer, no account, unsubscribe in one click.
Site address
TEN ROD ROAD AND CAPITOL CIRCLE
City
ROCHESTER
State
NH
ZIP
03839
Mailing
7 CRANE WAY, HOOKSETT, NH 03106
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237130
Employees
25
Ownership type
A

3 citations on file for this inspection.

1926.97 C02 I

Serious Gravity 10 1 instance 1 exposed
Issued
Oct 26, 2021
Penalty
Initial $5,461 · Current $5,461
29 CFR  1926.97(c)(2)(i): Electrical protective equipment did not conform with the maximum use voltage listed in Table E-4   29 CFR  1926.960(g)(5):The employer did not ensure that each employee exposed to 34.5 kv electrical hazards used protective equipment rated for the voltages they were exposed to.
Recent events (1)
  • — Z (S) $5461

1926.97 C02 VIII

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 26, 2021
Penalty
Initial $0 · Current $0
29 CFR  1926.97(c)(2)(viii):Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and the maximum intervals between tests were not in accordance with Table E-4 and Table E-5.  Location: site on or about 8/31/21, The employer did not ensure the rubber insulating sleeves used by an employee had been tested within the limits of table 5. The sleeves had a stamped test date which was just over two years prior to this current use.
Recent events (1)
  • — Z (S) $0

1926.960 C01 III B

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 26, 2021
Penalty
Initial $3,901 · Current $3,901
29 CFR  1926.960(c)(1)(iii)(B):The employer did not ensure energized parts were insulated when conductive objects  were taken closer than the  employer's established minimum approach distance.  Location: site On or about 8/31/21 the employer did not ensure employees were protected from an electrocution hazard when using a Milwaukee 18 volt impact gun in reach an uninsulated 34.5kv primary line.
Recent events (1)
  • — Z (S) $3901