DOVER PLAINS, NY —
OSHA Inspection: US LUMBER COMPANY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of US LUMBER COMPANY in 528 OLD ROUTE 22, DOVER PLAINS, NY 12522 (NAICS 321113). OSHA activity number 345510036.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- US LUMBER COMPANY
- Site address
- 528 OLD ROUTE 22
- City
- DOVER PLAINS
- State
- NY
- ZIP
- 12522
- Mailing
- P.O BOX 1139, DOVER PLAINS, NY 12522
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321113
- Employees
- 8
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.332 B01
- Issued
- Feb 17, 2022
- Abate by
- Mar 10, 2022
- Penalty
- Initial $13,052 · Current $0 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: (a) Sawmill building electrical room, during maintenance and cleaning of 480v 3 phase MCC bucket(s): On or prior to 8/23/21, employees were not trained in safety-related work practices including, but not limited to: hazards of arc flash, work procedures to avoid arc flash hazards, and the use and selection of tools and personal protective equipment to minimize risk of arc flash injury.
Recent events (3)
- — F (S) $0
- — C (S) $13052
- — Z (S) $13052
1910.333 A
- Issued
- Feb 17, 2022
- Abate by
- Mar 10, 2022
- Penalty
- Initial $13,052 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized: (a) Sawmill building electrical room, during maintenance and cleaning of 480v 3 phase MCC bucket(s): On or prior to 8/20/21, employees did not utilize safety related work practices including, but not limited to: de-energizing and locking out electrical equipment, using appropriate personal protective equipment, and using insulated tools.
Recent events (3)
- — F (S) $0
- — C (S) $13052
- — Z (S) $13052
1910.335 A01 I
- Issued
- Feb 17, 2022
- Abate by
- Mar 10, 2022
- Penalty
- Initial $13,052 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: (a) Sawmill building electrical room, during maintenance and cleaning of 480v 3 phase MCC bucket(s): On or prior to 8/23/21, employees were not provided with arc flash personal protective equipment, including, but not limited to fire resistant clothing, eye/face protection, and protective gloves.
Recent events (3)
- — F (S) $0
- — C (S) $13052
- — Z (S) $13052
More inspections in this industry (NAICS 321113)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345510036.