Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TIDEWATER LOGISTICS, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of TIDEWATER LOGISTICS, INC. in 440 SOUTH THIRD STREET, STEUBENVILLE, OH 43952 (NAICS 213112). OSHA activity number 345522189.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tidewater Logistics, INC. — free Get an email when a new federal OSHA severe-injury report for Tidewater Logistics, INC. is published. One employer, no account, unsubscribe in one click.
Site address
440 SOUTH THIRD STREET
City
STEUBENVILLE
State
OH
ZIP
43952
Mailing
706 AVIATOR DRIVE, FORT WORTH, TX 76179
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213112
Employees
42
Ownership type
A

5 citations on file for this inspection.

5(a)(1)

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Dec 13, 2021
Abate by
Dec 30, 2021
Penalty
Initial $9,557 · Current $0 Reduced
OSH ACT of 1970 Section (5)(a)(1):The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to electrical shock hazards.   a. On or about September 9, 2021, a Magnetic Lifting Technologies US (MLTUS) electrically-operated magnetic lifting device (Serial number 13016) was used by employees to move scrap material with a Link-Belt Material Handler, model 600LX. The insulation of the electrical wiring to the magnet was damaged to the bare conductors, exposing employees to an electrical shock hazard up to 230 volts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $9557

1910.157 C01

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 13, 2021
Abate by
Dec 23, 2021
Penalty
Initial $6,827 · Current $4,096 Reduced
29 CFR  1910.157(c)(1):The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury.  a. On or before September 9, 2021, the employer did not ensure fire extinguishers were provided to employees. Employees operated a loader without having a fire extinguisher accessible, thereby exposing the employees to fire hazards.
Recent events (2)
  • — I (S) $4096.2
  • — Z (S) $6827

1910.212 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Dec 13, 2021
Abate by
Dec 30, 2021
Penalty
Initial $9,557 · Current $5,734 Reduced
29 CFR  1910.212(a)(1):Types of guarding. One or more methods of machine guarding shall be provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks. Examples of guarding methods are-barrier guards, two-hand tripping devices, electronic safety devices, etc.  a. On or before September 9, 2021, the employer did not ensure employees were protected from coming into contact with the rotating conveyor belt and roller of Conveyor 1 in Building 38. The existing guard did not adequately protect employees from coming into contact with the rotating conveyor belt and roller, thereby exposing employees to caught-in hazards.  b. On or before September 9, 2021, the employer did not ensure employees were protected from coming into contact with the rotating conveyor belt and roller of Conveyor 2 in Building 38. The existing guard did not adequately protect employees from coming into contact with the rotating conveyor belt and roller, thereby exposing employees to caught-in hazards.
Recent events (2)
  • — I (S) $5734.2
  • — Z (S) $9557

1910.305 B01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 13, 2021
Penalty
Initial $6,827 · Current $4,096 Reduced
29 CFR  1910.305(b)(1)(i):Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed.  a. On or before September 9, 2021, the employer did not ensure that the conductors that entered boxes were protected from abrasion that the openings were effectively closed. The conductors entering the box of the Sun-Mite Infrared heater were exposed to the edge of the box where the connector was loose and pulled away from the box, thereby exposing employees to a 480 volt electrical contact hazard.
Recent events (2)
  • — I (S) $4096.2
  • — Z (S) $6827

1910.334 A03 I

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 13, 2021
Penalty
Initial $6,827 · Current $4,096 Reduced
29 CFR  1910.334(a)(3)(i):A flexible cord used with grounding type equipment shall contain an equipment grounding conductor.  a. On or before September 9, 2021, the employer did not ensure that flexible cords contained an equipment grounding conductor. Employees used a two wire extension cord that did not have a ground conductor to supply power to a diesel fuel pump, thereby exposing employees to a 110 volt electrical contact hazard.
Recent events (2)
  • — I (S) $4096.2
  • — Z (S) $6827

View Tidewater Logistics, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345522189.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.