OSHA Inspection: SAV-MOR COOLING & HEATING INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of SAV-MOR COOLING & HEATING INC. in CT TRANSIT 100 LEIBERT ROAD, HARTFORD, CT 06120 (NAICS 238220). OSHA activity number 345613616.

Watch Sav-Mor Cooling & Heating INC. — free Get an email when a new federal OSHA severe-injury report for Sav-Mor Cooling & Heating INC. is published. One employer, no account, unsubscribe in one click.
Site address
CT TRANSIT 100 LEIBERT ROAD
City
HARTFORD
State
CT
ZIP
06120
Mailing
231 CAPTAIN LEWIS DRIVE, SOUTHINGTON, CT 06489
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238220
Employees
24
Ownership type
A

4 citations on file for this inspection.

1910.28 B07

Deleted Serious Gravity 5 21 instances 1 exposed
Issued
Abate by
Penalty
Initial $3522.00 · Current $0.00 Reduced
29 CFR  1910.28(b)(7):  The employer did not ensure that each employee on a walking-working surface near an opening, including one with a chute attached, where the inside bottom edge of the opening is less than 39 inches (99 cm) above that walking-working surface and the outside bottom edge of the opening is 4 feet (1.2 m) or more above a lower level is protected from falling by the use of one of the systems listed in 29 CFR 1910.28(b)(7)(i)-(iv):   Jobsite located at the CT Transit terminal, 100 Leibert Road, Hartford, Connecticut:  From September 20, 2021 to November 3, 2021, an employee was required to enter approximately twenty one VS roof mounted units to perform preventative maintenance.    The employee was exposed to a fall distance of approximately nine feet from the catwalk/ledge into the duct system due to the open spaces between the interior catwalk and the edges of the opening leading into the duct system.
Recent events (3)
  • — F (S) $0
  • — C (S) $3522
  • — Z (S) $3522

1910.146 C04

Other-than-serious Gravity 5 21 instances 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $1200.00
29 CFR  1910.146(c)(4):  When the employer decided that its employees would enter permit spaces, the employer did not develop and implement a written permit space entry program that complied with 29 CFR 1910.146:  Jobsite located at the CT Transit terminal, 100 Leibert Road, Hartford, Connecticut:  From September 20, 2021 to November 3, 2021, an employee was required to enter approximately twenty one VS roof mounted units to perform preventative maintenance.   The VS enclosure where the employee walked across and stood on an interior catwalk was classified as a permit required confined space due the potential fall hazard down into the interior of ductwork system.  The employer had not developed and implemented procedures for employees to enter the space.
Recent events (3)
  • — F (O) $1200
  • — C (S) $0
  • — Z (S) $0

1910.332 B01

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $3522.00 · Current $0.00 Reduced
29 CFR  1910.332(b)(1):  Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  Jobsite located at the CT Transit terminal, 100 Leibert Road, Hartford, Connecticut:  On, or about, September 29, 2021, an employees who were required to work on and around energize electrical parts in order to maintain roof mounted HVAC units had not been provided with training regarding electrical safety related work practices to protect themselves against electrical shock, arc flash and blast hazards.
Recent events (3)
  • — F (S) $0
  • — C (S) $3522
  • — Z (S) $3522

1910.335 A01 I

Other-than-serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $1200.00
29 CFR  1910.335(a)(1)(i):  Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  Jobsite located at the CT Transit terminal, 100 Leibert Road, Hartford, Connecticut:  On, or about, September 29, 2021, an employee who was required to open access doors on Trane HVAC units was exposed to live electrical parts in order to de-energize the units and test for absence of voltage.  The employee was not provided with appropriate personal protective equipment such as, but not limited to, fire resistive clothing, a fire resistive face shield, a fire resistive balaclava, hearing protection and voltage rated gloves with protective leather gloves.