Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DEPARTMENT OF THE NAVY, NAVAL SUPPLY SYSTEMS COMMAND (NAVSUP)

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of DEPARTMENT OF THE NAVY, NAVAL SUPPLY SYSTEMS COMMAND (NAVSUP) in RED HILL BULK FUEL STORAGE FACILITY ICARUS WAY, HONOLULU, HI 96819 (NAICS 424710). OSHA activity number 345636682.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Department of the Navy, Naval Supply Systems Command (Navsup) — free Get an email when a new federal OSHA severe-injury report for Department of the Navy, Naval Supply Systems Command (Navsup) is published. One employer, no account, unsubscribe in one click.
Site address
RED HILL BULK FUEL STORAGE FACILITY ICARUS WAY
City
HONOLULU
State
HI
ZIP
96819
Mailing
1942 GAFFNEY STREET SUITE 100 BLDG 1757 2ND FLOOR, PEARL HARBOR, HI 96860
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424710
Employees
15
Ownership type
D

2 citations on file for this inspection.

1910.106 F08

Deleted Serious Gravity 10 1 instance 20 exposed
Issued
Mar 3, 2022
Abate by
Apr 19, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.106(f)(8): Additional fire-control equipment was not provided as required for a tank of more than 50,000 gallons individual capacity containing Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C), and where an unusual exposure hazard existed from surrounding property. Such additional fire-control equipment shall be sufficient to extinguish a fire in the largest tank. The design and amount of such equipment shall be in accordance with approved engineering standards:   Tank Gallery underground tunnel: The AFFF fire suppression system for the 12-million gallon storage tanks which contained hydrocarbon fuels, was disabled and locked out for more than a year.  Welding and hot work on the tanks, and the tank gallery area of the tunnel was ongoing. Alternative firefighting measures were not put in place, exposing employees to fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.160 B02

Serious Gravity 10 1 instance 20 exposed
Issued
Mar 3, 2022
Abate by
Apr 19, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.160(b)(2): The employer did not notify employees and take the necessary temporary precautions to assure their safety when the fixed extinguishing system became inoperable.   Tank Gallery underground tunnel:  The AFFF fire suppression system was disabled and locked out for more than a year. Alternative firefighting measure were not put in place and employees working in the tunnel were not notified of the condition of the AFFF system. Employees were exposed to fire hazards.