Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BRUMBAUGH LUMBER LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BRUMBAUGH LUMBER LLC in 16460 CROGHAN PIKE, SHIRLEYSBURG, PA 17260 (NAICS 321113). OSHA activity number 345642847.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Brumbaugh Lumber LLC — free Get an email when a new federal OSHA severe-injury report for Brumbaugh Lumber LLC is published. One employer, no account, unsubscribe in one click.
Site address
16460 CROGHAN PIKE
City
SHIRLEYSBURG
State
PA
ZIP
17260
Mailing
16460 CROGHAN PIKE, SHIRLEYSBURG, PA 17260
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321113
Employees
17
Ownership type
A

3 citations on file for this inspection.

1910.303 G01 II

Serious Gravity 1 1 instance 16 exposed
Issued
Apr 11, 2022
Penalty
Initial $2,113 · Current $1,350 Reduced
29 CFR  1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  a. Near the trim saw - On or about November 17, 2021, the top of the 480 electrical control panel for the trim saw was being used as a storage shelf for flammable and combustible materials, exposing employees to a fire hazard.  Corrected during inspection - No Abatement Required
Recent events (2)
  • — I (S) $1350
  • — Z (S) $2113

1910.305 B01 II

Serious Gravity 5 2 instances 16 exposed
Issued
Apr 11, 2022
Penalty
Initial $2,818 · Current $1,350 Reduced
29 CFR  1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   a. In the common room - On or about November 17, 2021, the Motor Control Center had five buckets that were not effectively closed, exposing employees, to an electrical or fire hazard.  b. In the chipper room - On or about November 17, 2021, the knife switch disconnect box for the Cutler Hammer, had an unused opening at the base allowing for wood dust and other material to enter,  creating an electrical, fire, and explosion hazard.  Corrected During Inspection - No Abatement Required
Recent events (2)
  • — I (S) $1350
  • — Z (S) $2818

1910.303 B02

Serious Gravity 5 1 instance 16 exposed
Issued
Apr 11, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   a. In the common room - On or about November 17, 2021,  the motor control center had five unused openings that were being closed with duct tape which is not listed or labeled for electrical installation suitability for 600 VAC, exposing employees to an electrical hazard.  Corrected During Inspection - No Abatement Required
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Brumbaugh Lumber LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345642847.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.