KISSIMMEE, FL —
OSHA Inspection: AMPRO, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of AMPRO, INC. in 1347 E. VINE STREET, KISSIMMEE, FL 34744 (NAICS 238210). OSHA activity number 345648646.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AMPRO, INC.
- Site address
- 1347 E. VINE STREET
- City
- KISSIMMEE
- State
- FL
- ZIP
- 34744
- Mailing
- 7818 PROFESSIONAL PL, TAMPA, FL 33637
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 45
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.333 A01
- Issued
- Feb 25, 2022
- Abate by
- Mar 23, 2022
- Penalty
- Initial $10,151 · Current $11,000
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them: a. On or about 11/11/2021, employees, prior to the replacing/ pole mounted light fixtures/ parking lot lights, did not de-energize and ground the circuits or effectively guard the circuits by insulation or other means nor had the employer demonstrated that de-energizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations; therefore exposing the employees to an electrocution hazard.
Recent events (2)
- — I (S) $11000
- — Z (S) $10151
1910.333 B02 III A
- Issued
- Feb 25, 2022
- Abate by
- Mar 23, 2022
- Penalty
- Initial $10,151 · Current $11,000
General-duty citation text
29 CFR 1910.333(b)(2)(iii)(A): A lock and a tag were not placed on each disconnecting means used to deenergize circuits and equipment on which work was to be performed: a. On or about 11/11/2021, employees, prior to the replacing/ installing pole mounted light fixtures/ parking lot lights, did not ensure that the controls that were to be deactivated during the course of work on energized or de-energized equipment or circuits were locked and tagged; therefore exposing the employees to an electrocution hazard.
Recent events (2)
- — I (S) $11000
- — Z (S) $10151
1910.333 B02 IV B
- Issued
- Feb 25, 2022
- Abate by
- Mar 23, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(iv)(B): Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that the circuit elements and equipment parts were deenergized. a. On or about 11/11/2021, employees, prior to the replacing/ installing pole mounted light fixtures/ parking lot lights, did not use an electrical detection instrument/ did not ensure that the light fixture wiring/ electrical power supply was not energized; therefore exposing the employees to an electrocution hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Feb 25, 2022
- Abate by
- Mar 23, 2022
- Penalty
- Initial $10,151 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a. On or about 11/11/2021, employees were replacing/ working below energized/ uninsulated pole mounted light fixtures/ parking lot lights and the related wiring, during which time the employees did not use/ did not wear rubber electrically insulated protective gloves; therefore exposing the employees to an electrocution hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $10151
1910.335 A01 IV
- Issued
- Feb 25, 2022
- Abate by
- Mar 23, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(iv): Employees exposed to the danger of head injury from electric shock or burns due to contact with exposed energized parts did not wear nonconductive head protection: a. On or about 11/11/2021, employees were replacing/ working below energized/ uninsulated pole mounted light fixtures/ parking lot lights and the related wiring, during which the employees did not use/ did not wear electrically insulated protective helmets; therefore exposing the employees to an electrocution hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A02 I
- Issued
- Feb 25, 2022
- Abate by
- Mar 23, 2022
- Penalty
- Initial $10,151 · Current $10,483
General-duty citation text
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts: a. On or about 11/11/2021, employees were replacing/ working below energized/ uninsulated pole mounted light fixtures/ parking lot lights and the related wiring, during which time the employees were using uninsulated hand tools to connect an energized wire; therefore exposing the employees to an electrocution hazard.
Recent events (2)
- — I (S) $10483.2
- — Z (S) $10151
More inspections at Ampro, INC.