MENA, AR —
OSHA Inspection: GPM INVESTMENTS, LLC
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of GPM INVESTMENTS, LLC in 1121 HIGHWAY 71 S, MENA, AR 71953 (NAICS 447110). OSHA activity number 345654115.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GPM INVESTMENTS, LLC
- Site address
- 1121 HIGHWAY 71 S
- City
- MENA
- State
- AR
- ZIP
- 71953
- Mailing
- 1121 HIGHWAY 71 S, MENA, AR 71953
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 447110
- Employees
- 6
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.37 A03
- Issued
- Dec 28, 2021
- Abate by
- Jan 10, 2022
- Penalty
- Initial $13,653 · Current $13,653
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: At the back storeroom, egress from the restroom was limited to approximately 12-inches by a table that had been placed in front of the door.
Recent events (2)
- — I (O) $13653
- — Z (S) $13653
1910.303 G01
- Issued
- Dec 28, 2021
- Abate by
- Jan 10, 2022
- Penalty
- Initial $11,703 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: In the storage room, access to the electrical panel was blocked by a metal table.
Recent events (2)
- — I (O) $0
- — Z (S) $11703
1910.303 B07 I
- Issued
- Dec 28, 2021
- Abate by
- Jan 10, 2022
- Penalty
- Initial $5,851 · Current $5,851
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxillary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substanially equivalent to the wall of the equipment: In the storage room, employees were required to utilize the breakers in the electrical control panel despite the presence of an uncovered knockout opening.: (a) the breaker box located closest to the sales area; (b) the breaker box located closest to the restroom.
Recent events (2)
- — I (O) $5851
- — Z (S) $5851
1910.304 G05
- Issued
- Dec 28, 2021
- Abate by
- Jan 10, 2022
- Penalty
- Initial $13,653 · Current $0 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: At the refrigerated display cooler, stray voltage in the amount of at least 57 volts AC was detected on both the exterior and interior.
Recent events (2)
- — I (S) $0
- — Z (S) $13653
More inspections at GPM Investments, LLC
View GPM Investments, LLC's full OSHA safety record →
More inspections in this industry (NAICS 447110)
More inspections in AR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345654115.