Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GPM INVESTMENTS, LLC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of GPM INVESTMENTS, LLC in 1121 HIGHWAY 71 S, MENA, AR 71953 (NAICS 447110). OSHA activity number 345654115.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch GPM Investments, LLC — free Get an email when a new federal OSHA severe-injury report for GPM Investments, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1121 HIGHWAY 71 S
City
MENA
State
AR
ZIP
71953
Mailing
1121 HIGHWAY 71 S, MENA, AR 71953
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
447110
Employees
6
Ownership type
A

4 citations on file for this inspection.

1910.37 A03

Other-than-serious Gravity 10 1 instance 6 exposed
Issued
Dec 28, 2021
Abate by
Jan 10, 2022
Penalty
Initial $13,653 · Current $13,653
29 CFR  1910.37(a)(3):   Exit route(s) were not kept free and unobstructed:   At the back storeroom, egress from the restroom was limited to approximately 12-inches by a table that had been placed in front of the door.
Recent events (2)
  • — I (O) $13653
  • — Z (S) $13653

1910.303 G01

Other-than-serious Gravity 5 1 instance 6 exposed
Issued
Dec 28, 2021
Abate by
Jan 10, 2022
Penalty
Initial $11,703 · Current $0 Reduced
29 CFR  1910.303(g)(1):   Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:   In the storage room, access to the electrical panel was blocked by a metal table.
Recent events (2)
  • — I (O) $0
  • — Z (S) $11703

1910.303 B07 I

Other-than-serious Gravity 1 4 instances 6 exposed
Issued
Dec 28, 2021
Abate by
Jan 10, 2022
Penalty
Initial $5,851 · Current $5,851
29 CFR  1910.303(b)(7)(i): Unused openings in boxes, raceways, auxillary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substanially equivalent to the wall of the equipment:   In the storage room, employees were required to utilize the breakers in the electrical control panel despite the presence of an uncovered knockout opening.: (a) the breaker box located closest to the sales area; (b) the breaker box located closest to the restroom.
Recent events (2)
  • — I (O) $5851
  • — Z (S) $5851

1910.304 G05

Deleted Serious Gravity 10 1 instance 6 exposed
Issued
Dec 28, 2021
Abate by
Jan 10, 2022
Penalty
Initial $13,653 · Current $0 Reduced
29 CFR  1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  At the refrigerated display cooler, stray voltage in the amount of at least 57 volts AC was detected on both the exterior and interior.
Recent events (2)
  • — I (S) $0
  • — Z (S) $13653

View GPM Investments, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345654115.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.