Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TRI-STATE ARMATURE AND ELECTRICAL WORKS, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of TRI-STATE ARMATURE AND ELECTRICAL WORKS, INC. in 100 HINO BOULEVARD, MARION, AR 72364 (NAICS 811310). OSHA activity number 345666630.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tri-State Armature and Electrical Works, INC. — free Get an email when a new federal OSHA severe-injury report for Tri-State Armature and Electrical Works, INC. is published. One employer, no account, unsubscribe in one click.
Site address
100 HINO BOULEVARD
City
MARION
State
AR
ZIP
72364
Mailing
330 GE PATTERSON AVENUE, MEMPHIS, TN 38101
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811310
Employees
5
Ownership type
A

2 citations on file for this inspection.

1910.147 F03 II D

Serious Gravity 10 5 instances 5 exposed
Issued
Mar 22, 2022
Abate by
Apr 1, 2022
Penalty
Initial $13,052 · Current $13,052
29 CFR  1910.147(f)(3)(ii)(D):Each authorized employee did not affix a personal lockout or tagout device to the group lockout device before working on the machine or equipment:  At the Hino Motors facility, located in Marion, Arkansas, on or about 11/26/2021, where five employees were exposed to electrical shock hazards while cleaning the switchgear in substation #7 with only one lock affixed to the disconnect arm.
Recent events (1)
  • — Z (S) $13052

1910.333 B02 IV B

Serious Gravity 10 1 instance 5 exposed
Issued
Mar 22, 2022
Abate by
Apr 1, 2022
Penalty
Initial $13,052 · Current $13,052
29 CFR  1910.333(b)(2)(iv)(B): Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that the switch gear was deenergized:   At the Hino Motors facility, located in Marion, Arkansas, on or about 11/26/2021, where five employees were exposed to electrical shock hazards while cleaning the switchgear in substation #7 where the infeed lugs were still energized with 13,800 volts.
Recent events (1)
  • — Z (S) $13052

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345666630.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.