OSHA Inspection: USGS

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of USGS in 6000 J STREET, SACRAMENTO, CA 95819 (NAICS 541715). OSHA activity number 345670129.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Usgs — free Get an email when a new federal OSHA severe-injury report for Usgs is published. One employer, no account, unsubscribe in one click.
Establishment
USGS
Site address
6000 J STREET
City
SACRAMENTO
State
CA
ZIP
95819
Mailing
6000 J STREET, SACRAMENTO, CA 95819
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541715
Employees
400
Ownership type
D

2 citations on file for this inspection.

1910.1450 E03 III

Serious Gravity 5 4 instances 30 exposed
Issued
Dec 29, 2021
Abate by
Mar 18, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.1450(e)(3)(iii):The employer did not ensure fume hoods and other protective equipment were functioning properly and did not implement specific measures to ensure proper and adequate performance of such equipment.  Placer Hall, USGS Labs,  CSUS - The following inadequacies were noted in the U.S. Geological Survey water quality research labs.  1. Organic Chemistry Lab, #1107 - The fume hood averaged less than 100 FPM flow rate with both the sash fully open and with the sash adjusted to a 12" opening across the face.  The hood velocity gauge was non-functioning. 2. Carbon Lab, #1110 - The fume hood averaged less than 100 FPM flow rate with both  sash fully open and with the sash adjusted to a 12" opening across  face. 3. Trace Metal, #1109 - The fume hood averaged less than 100 FPM flow rate with both the sash fully open and with the sash adjusted to a 12" opening across the  face. 4.  Biology Lab, #1111 -  The fume hood averaged less than 100 FPM flow rate with both the sash fully open and with the sash adjusted to a 12" opening across  face.  *Note -  Low flow rate alarms were observed going off during normal work use.
Recent events (3)
  • — P (S) $0
  • — P (S) $0
  • — Z (S) $0

1910.157 C01

Other-than-serious 1 instance 30 exposed
Issued
Dec 29, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.157(c)(1): 29 CFR 1910.157(c)(1):  Portable Fire Extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:   Organic Chem. Lab, CSUS - A portable fire extinguisher was free standing on a lab counter and obstructed by lab materials. Lab employees use flammable materials and are expected to use the fire extinguishers in the event of a fire.  Employees are exposed to fire hazards.
Recent events (1)
  • — Z (O) $0

View Usgs's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345670129.