Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: EMPIRE ELECTRIC, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of EMPIRE ELECTRIC, INC. in 3269 UNIVERSITY BLVD NORTH, JACKSONVILLE, FL 32277 (NAICS 238210). OSHA activity number 345693212.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Empire Electric, INC. — free Get an email when a new federal OSHA severe-injury report for Empire Electric, INC. is published. One employer, no account, unsubscribe in one click.
Site address
3269 UNIVERSITY BLVD NORTH
City
JACKSONVILLE
State
FL
ZIP
32277
Mailing
5810 MACY AVENUE, JACKSONVILLE, FL 32211
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
24
Ownership type
A

4 citations on file for this inspection.

1910.333 A

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 9, 2022
Penalty
Initial $3,522 · Current $3,522
29 CFR  1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized:  a. In the electrical service room of building 3269 at University Place Apartments, Jacksonville, FL: On or about December 14, 2021, the employer exposed the qualified lead electrician and electrician helper to arc flash hazards, in that safety related work practices were not employed when the lead electrician changed out a 100 amp breaker within the energized 240VAC 600 Amp panel.
Recent events (1)
  • — Z (S) $3522

1910.335 A01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 9, 2022
Penalty
Initial $3,522 · Current $3,522
29 CFR  1910.335(a)(1)(i):Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  a. In the electrical service room of building 3269 at University Place Apartments, Jacksonville, FL: On or about December 14, 2021, the employer exposed the qualified lead electrician and electrician helper to electrical and arc-flash hazards, in that hazard risk category 1 electrical arc-flash protective equipment and arc-flash clothing hard hat, hearing protection, and rubber insulated gloves were not used when the lead electrician changed out a 100 amp breaker within the energized 240VAC 600 Amp panel.
Recent events (1)
  • — Z (S) $3522

1910.335 A01 V

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 9, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.335(a)(1)(v):Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face:  a. In the apartment building 3269 electrical service room, located at University Place Apartments, 3269 University Blvd. N., Jacksonville, FL: On or about December 14, 2021 and at times prior, the employer exposed the qualified lead electrician and electrician helper to electrical and arc-flash hazards, in that hazard risk category 1 electrical arc-flash protective equipment faceshields were not used when the lead electrician changed out a 100 amp breaker within the energized 240VAC 600 Amp panel.
Recent events (1)
  • — Z (S) $0

1910.335 A02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 9, 2022
Abate by
Jul 28, 2022
Penalty
Initial $3,522 · Current $3,522
29 CFR  1910.335(a)(2)(i):When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts:  a. In the electrical service room of building 3269 at University Place Apartments, Jacksonville, FL: On or about December 14, 2021, the employer exposed the qualified lead electrician and electrician helper to electrical and arc-flash hazards, in that hazard risk category 1 electrical arc-flash protective equipment insulated hand tools were not used when the lead electrician changed out a 100 amp breaker within the energized 240VAC 600 Amp panel.
Recent events (1)
  • — Z (S) $3522

View Empire Electric, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345693212.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.