Safety Incidents OSHA Severe Injury Reports · 2015–2025
3,913,242Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: GST MANUFACTURING LTD

Follow-up inspection · Safety discipline

On , OSHA opened a follow-up safety inspection of GST MANUFACTURING LTD in 4201 JANADA STREET, HALTOM CITY, TX 76117 (NAICS 332312). OSHA activity number 345711501.

Watch GST Manufacturing LTD — free Get an email when a new federal OSHA severe-injury report for GST Manufacturing LTD is published. One employer, no account, unsubscribe in one click.
Site address
4201 JANADA STREET
City
HALTOM CITY
State
TX
ZIP
76117
Mailing
4201 JANADA STREET, HALTOM CITY, TX 76117
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332312
Employees
150
Ownership type
A

4 citations on file for this inspection.

1910.253 B02 II

Serious Gravity 1 2 instances 4 exposed
Issued
Penalty
Initial $4754.00 · Current $2852.00 Reduced
29 CFR  1910.253(b)(2)(ii): Assigned storage spaces for cylinders was not located away from elevators, stairs, or gangways where cylinders could not be knocked over or damaged by passing or falling objects, or subject to tampering by unauthorized persons.     On January 4, 2022, and times prior thereto, in the south weld section, a compressed gas cylinder was not chained or secured from falling exposing employee(s ) to potential struck-by hazards.
Recent events (2)
  • — I (S) $2852.4
  • — Z (S) $4754

1910.305 B02

Other-than-serious 2 instances 4 exposed
Issued
Penalty
Initial $1047.00 · Current $628.00 Reduced
29 CFR  1910.305(b)(2):Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose.   On January 4, 2022, and times prior thereto, the employer did not provide a cover plates over the junction boxes with exposed wires exposing employees to electrical shock hazards.
Recent events (2)
  • — I (O) $628.2
  • — Z (O) $1047

1910.334 A02 I

Other-than-serious 2 instances 4 exposed
Issued
Penalty
Initial $1047.00 · Current $628.00 Reduced
29 CFR  1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket).  On January 4, 2022, and times prior thereto, in the Robotic Weld section, the employer used an extension cord with a missing ground pin to energize small portable tools and floor fan exposing employees to electrical shock hazards.
Recent events (2)
  • — I (O) $628.2
  • — Z (O) $1047

1910.334 A02 II

Deleted Other-than-serious 2 instances 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service:  On January 4, 2022, and times prior thereto, in the Robotic Weld section, the employer failed to remove a defective extension cord with a missing ground pin where employees exposed to a injury such as shock hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View GST MANUFACTURING LTD's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345711501.