LINCOLN, NE —
OSHA Inspection: SCHNEIDER ELECTRIC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of SCHNEIDER ELECTRIC in 1717 CENTER PARK ROAD, LINCOLN, NE 68512 (NAICS 335313). OSHA activity number 345723944.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SCHNEIDER ELECTRIC
- Site address
- 1717 CENTER PARK ROAD
- City
- LINCOLN
- State
- NE
- ZIP
- 68512
- Mailing
- 1717 CENTER PARK ROAD, LINCOLN, NE 68512
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 335313
- Employees
- 490
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.212 A01
- Issued
- Feb 24, 2022
- Abate by
- Mar 22, 2022
- Penalty
- Initial $14,502 · Current $14,502
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: The employer failed to prevent an employee from bypassing an interlocked guard which exposed the employee to a hazard. This was documented at 1717 Center Park Road, Lincoln, Nebraska on January 13, 2022. The employer failed to ensure that an employee could not bypass the interlocked guard to the blast chamber rotors of a press cleaning machine while the rotors were still moving after the emergency stop was engaged. The injured employee inadvertently disabled the area access interlock through inappropriate use of an emergency stop button instead of use of the written lockout tagout procedure on which he had been trained.
Recent events (2)
- — I (O) $14502
- — Z (S) $14502
1910.303 B02
- Issued
- Feb 24, 2022
- Abate by
- Mar 22, 2022
- Penalty
- Initial $9,116 · Current $6,331 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling. The employer is failing to ensure that all employees are not exposed to electrical shock hazards. This was most recently documented at 1717 Center Park Road, Lincoln, Nebraska on January 13, 2022 when employees were found to be working near a junction box designed for fixed location being used as a pendant drop in the Molding Department.
Recent events (2)
- — I (O) $6331
- — Z (S) $9116
1910.305 B01 I
- Issued
- Feb 24, 2022
- Abate by
- Mar 22, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
9 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed: The employer is failing to ensure that all employees are not exposed to electrical shock hazards. This was most recently documented at 1717 Center Park Road, Lincoln, Nebraska on January 13, 2022 when employees were found to be working near exposed energized electrical wiring in the Molding Department.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Schneider Electric
View Schneider Electric's full OSHA safety record →
More inspections in this industry (NAICS 335313)
More inspections in NE
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345723944.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.