Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: E-MC ELECTRICAL SERVICES

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of E-MC ELECTRICAL SERVICES in 2004 EAST RANDOL MILL ROAD, ARLINGTON, TX 76011 (NAICS 238210). OSHA activity number 345741391.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch E-MC Electrical Services — free Get an email when a new federal OSHA severe-injury report for E-MC Electrical Services is published. One employer, no account, unsubscribe in one click.
Site address
2004 EAST RANDOL MILL ROAD
City
ARLINGTON
State
TX
ZIP
76011
Mailing
2004 EAST RANDOL MILL ROAD, ARLINGTON, TX 76011
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
21
Ownership type
A

4 citations on file for this inspection.

1910.333 A

Serious Gravity 1 1 instance 4 exposed
Issued
Feb 22, 2022
Abate by
Mar 22, 2022
Penalty
Initial $2,486 · Current $1,492 Reduced
29 CFR  1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized.    On January 18, 2022, at Hurricane Harbor parking lot, the employer did not ensure safety related work practices was used when working at or near electricity exposing the employee to arc flash hazards.
Recent events (2)
  • — I (S) $1491.6
  • — Z (S) $2486

1910.333 A01

Serious Gravity 10 1 instance 4 exposed
Issued
Feb 22, 2022
Abate by
Mar 22, 2022
Penalty
Initial $5,801 · Current $3,481 Reduced
29 CFR  1910.333(a)(1): Live parts that the employee was exposed to were not de-energized before the work began in or near them.    On January 18, 2022, the employer did not ensure the transformer was de-energized prior to the employee working near an electrical breaker box exposing the employee to arc flash hazards.
Recent events (2)
  • — I (S) $3480.6
  • — Z (S) $5801

1910.333 A02

Serious Gravity 10 1 instance 4 exposed
Issued
Feb 22, 2022
Abate by
Mar 22, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.333(a)(2): Where exposed live parts were not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices were not used to protect employees who could be exposed to the electrical hazards involved:   On January 18, 2022, the employer did not ensure the employee working on or near electrical live parts had proper safety equipment such as gloves and sleeves exposing the employee to arc flash burn hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 B01

Serious Gravity 1 1 instance 4 exposed
Issued
Feb 22, 2022
Abate by
Mar 22, 2022
Penalty
Initial $2,486 · Current $1,492 Reduced
29 CFR  1910.333(b)(1): The employer did not ensure that exposed deenergized parts were locked out and tagged in accordance with paragraph (b) and treated them as energized parts.  On January 18, 2022, the employer did not ensure employees began working around live parts until ONCOR deenergized the transformer exposing the employee to arc flash burn hazards.
Recent events (2)
  • — I (S) $1491.6
  • — Z (S) $2486

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345741391.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.