CORPUS CHRISTI, TX —
OSHA Inspection: BUCKEYE TEXAS PROCESSING, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BUCKEYE TEXAS PROCESSING, LLC in 7209 UP RIVER ROAD, CORPUS CHRISTI, TX 78409 (NAICS 324110). OSHA activity number 345776157.
Where did this inspection happen?
- Establishment
- BUCKEYE TEXAS PROCESSING, LLC
- Site address
- 7209 UP RIVER ROAD
- City
- CORPUS CHRISTI
- State
- TX
- ZIP
- 78409
- Mailing
- 7209 UP RIVER ROAD, CORPUS CHRISTI, TX 78409
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 89
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.119 J02
- Issued
- Abate by
- Penalty
- Initial $14502.00 · Current $14502.00
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going integrity of process equipment: a) On or about 02/09/2022, at the Buckeye Texas Processing (BTP) facility in Corpus Christi Texas, the employer failed to ensure that written procedures for testing or inspecting of the emergency shutdown button "Unit 100 ESD" (or tag 100-ESD-0133) were established. b) On or about 02/09/2022, at the Buckeye Texas Processing (BTP) facility in Corpus Christi Texas, the employer failed to ensure that written procedures for testing or inspecting of process equipment were established for the following devices : I. Level Control LIC- 0405 (P&ID 100-PID-104 No.10) II. Level Indicator LI-0413 (P&ID 100-PID-104 No.10) III. Pressure Transmitter PT-1228 (P&ID 100-PID-112 No.5) IV. Interlock I-10 (P&ID 100-PID-111 No.7) V. Temperature indicator/control TI/TIC-1305 (P&ID 100-PID-113 No.12) VI. Level indicator LI-1328 (P&ID 100-PID-113 No.12)
Recent events (2)
- — I (O) $14502
- — Z (S) $14502
1910.119 J04 I
- Issued
- Abate by
- Penalty
- Initial $14502.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.119(j)(4)(i): The employer did not perform inspections and tests on process equipment: a) On or about 02/09/2022, at the Buckeye Texas Processing (BTP) facility in Corpus Christi Texas, the employer did not perform inspections and testing on the emergency shutdown button "Unit 100 ESD" (or tag 100-ESD-0133) located in the control room. b) On or about 02/09/2022, at the Buckeye Texas Processing (BTP) facility in Corpus Christi Texas, the employer did not perform inspections and testing on the following devices: I. Level control LIC- 0405 (P&ID 100-PID-104 No.10) II. Level indicator LI-0413 (P&ID 100-PID-104 No.10) III. Pressure transmitter PT-1228 (P&ID 100-PID-112 No.5) IV. Interlock I-10 (P&ID 100-PID-111 No.7) V. Temperature indicator/control TI/TIC-1305 (P&ID 100-PID-113 No.12) VI. Level indicator LI-1328 (P&ID 100-PID-113 No.12) c) On or about 02/09/2022, at the Buckeye Texas Processing (BTP) facility in Corpus Christi Texas, the employer did not perform inspections and testing on the following pressure relief valves including but not limited to: I. Pressure safety valve PSV- 0410 (P&ID 100-PID-104 No.10). II. Pressure safety valve PSV-0113A and PSV-0113B (P&ID 100-PID-101 No.1)
Recent events (2)
- — I (O) $0
- — Z (S) $14502
1910.119 F03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.119(f)(3): The operating procedures were not reviewed as often as necessary to assure that they reflect current operating practice, including changes that result from changes in process chemicals, technology, and equipment, and changes to facilities. The employer did not annually certify that operating procedures were current and accurate: a) On or about 02/09/2022, at the Buckeye Texas Processing (BTP) facility in Corpus Christi Texas, the employer did not annually certify operating procedures for unit 100 to ensure that they are current and accurate.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.119 L03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.119(l)(3): Employees involved in operating a process and maintenance and contract employees whose job tasks would be affected by a change in the process were not informed of and trained in the change prior to start-up of the process or affected part of the process: a) On or about 02/09/2022, at the Buckeye Texas Processing (BTP) facility in Corpus Christi Texas, the employer did not inform affected employees of a change in the process (installing a permanent level switch to control 100-P-2604 start and stop command) through a management of change, MOC BTP-22-MOC012 (Temporary MOC BTP021-MOC067) prior to start-up of the process.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.146 C02
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.146(c)(2): When workplace contained permit spaces, the employer did not inform exposed employees, by posting danger signs or by any other equally effective means, of the existence and location of and the danger posed by the permit spaces. NOTE: A sign reading DANGER -- PERMIT-REQUIRED CONFINED SPACE, DO NOT ENTER or using other similar language would satisfy the requirement for a sign. a) On or about 02/09/2022, at the Buckeye Texas Processing (BTP) facility in Corpus Christi Texas, the employer did not inform employees by posting danger signs or by any other equally effective means on workplace contains permit spaces for the Main Crude Fractionator, 200-T-101, skirt and the Side Strippers, 200-T-102 (Heavy Naphtha), 200-T-103 (Kerosene) and 200-T-104 (Gas Oils) skirt (These strippers are stacked on a top each other to form one tower).
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G02 III
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(2)(iii): Entrances to rooms and other guarded locations containing exposed live parts were not marked with conspicuous warning signs forbidding unqualified persons to enter: a) On or about 02/09/2022, at the Buckeye Texas Processing (BTP) facility in Corpus Christi Texas, the electrical room/ motor control center (MCC) rooms 1000, 3000 and 5000 were not marked with conspicuous warning signs forbidding unqualified persons to enter.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 324110)
EL SEGUNDO, CA—2026-06-30
CHEVRON U.S.A. INC.
EL SEGUNDO, CA—2026-06-30
CHEVRON U.S.A. INC.
TRAINER, PA—2026-06-26
MONROE ENERGY, LLC
RICHMOND, CA—2026-06-17
CHEVRON U.S.A. INC.
WILMINGTON, CA—2026-06-10
MARATHON LOS ANGELES REFINERY - WILMINGTON
More inspections in TX
SPRING, TX—2026-07-10
DORSTENER WIRE TECH INC.