Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NORTHERN MANOR MULTICARE CENTER, INC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of NORTHERN MANOR MULTICARE CENTER, INC in 199 N MIDDLETOWN RD., NANUET, NY 10954 (NAICS 623110). OSHA activity number 345799191.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Northern Manor Multicare Center, INC — free Get an email when a new federal OSHA severe-injury report for Northern Manor Multicare Center, INC is published. One employer, no account, unsubscribe in one click.
Site address
199 N MIDDLETOWN RD.
City
NANUET
State
NY
ZIP
10954
Mailing
199 N MIDDLETOWN RD., NANUET, NY 10954
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623110
Employees
270
Ownership type
A

3 citations on file for this inspection.

1910.1000 A02

Serious Gravity 10 1 instance 20 exposed
Issued
May 11, 2022
Penalty
Initial $14,502 · Current $8,110 Reduced

Hazardous substances C730

29 CFR  1910.1000(a)(2): Employees were exposed to an airborne concentration of Carbon Monoxide listed in Table Z-1 in excess of the 8-hour Time-Weighted Average concentration of 50 parts per million (50 ppm) particles of air for any 8-hour work shift of a 40-hour work week and attenuated accordingly for extended work shifts in extended work weeks:  Location: Basement kitchen  a) On or about November 13, 2021 an employee was using a six-burner, Garland M44R stove intended to be vented by a an exhaust hood. The exhaust hood was not turned on resulting in the employee being exposed to 220.2 ppm of Carbon Monoxide, which is 4.404 times over the OSHA permissible exposure limit (PEL) of 50 ppm during an 8-hour shift.
Recent events (2)
  • — I (S) $8110
  • — Z (S) $14502

1910.1000 E

Serious Gravity 10 1 instance 20 exposed
Issued
May 11, 2022
Abate by
Aug 12, 2022
Penalty
Initial $0 · Current $0

Hazardous substances C730

29 CFR  1910.1000(e): Feasible administrative or engineering controls were not determined and implemented to achieve compliance with the limits prescribed in 29 CFR 1910.1000(a) through (d):  a) On or about November 13, 2021 an employee was using a six-burner, Garland M44R. The employer did not ensure the ventilation system for the stove was operational. As a result, the employee was  exposed to 220.2 ppm of Carbon Monoxide, and is above the OSHA permissible exposure limit (PEL) of 50 ppm during an 8-hour shift.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1904.39 A02

Other-than-serious 1 instance 1 exposed
Issued
May 11, 2022
Penalty
Initial $1,500 · Current $1,500
29 CFR  1904.39(a)(2): The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye.  Location: Basement kitchen  a) On or about November 13, 2021, the employer did not report the hospitalization of an employee due to carbon monoxide exposure within the required 24-hour timeframe.
Recent events (2)
  • — I (O) $1500
  • — Z (O) $1500

View Northern Manor Multicare Center, INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345799191.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.