Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MCI WEST - MCB CAMP PENDLETON FACILITIES MAINTENANCE SUSTAINMENT DIVISION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MCI WEST - MCB CAMP PENDLETON FACILITIES MAINTENANCE SUSTAINMENT DIVISION in BUILDING 2296, CAMP PENDLETON, CA 92055 (NAICS 561210). OSHA activity number 345802524.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch MCI West - MCB Camp Pendleton Facilities Maintenance Sustainment Division — free Get an email when a new federal OSHA severe-injury report for MCI West - MCB Camp Pendleton Facilities Maintenance Sustainment Division is published. One employer, no account, unsubscribe in one click.
Site address
BUILDING 2296
City
CAMP PENDLETON
State
CA
ZIP
92055
Mailing
AC/S, G-F (FACILITIES) BOX 555013, CAMP PENDLETON, CA 92055
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561210
Employees
123
Ownership type
D

9 citations on file for this inspection.

1910.28 B01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 29, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.28(b)(1)(i): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level was protected from falling:  Sign Shop, Loft: On and/or before February 24, 2022 employee(s) used a vertical ladder to access a loft that was measured approximately 9 feet 3 inches above a lower level. The employer did not ensure the loft access area was protected by the use of guardrail systems or personal fall arrest systems. Employee(s) were exposed to a 9-foot fall hazard.
Recent events (1)
  • — Z (S) $0

1910.157 E03

Serious Gravity 5 5 instances 101 exposed
Issued
Mar 29, 2022
Abate by
Apr 22, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  On and/or before February 24, 2022 employee(s) occupy the following shops in the performance of their assigned trades and tasks. The fire extinguishers in the following locations had not been subjected to their annual maintenance check(s). This condition potentially exposes employee(s) to fire and/or emergency evacuation hazard(s)  In the following location(s):   a) Pipe Shop b) Pipe Shop Supply Shed  c) Sign Shop  d) Carpenter Shop  e) Metal Shop
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 4 instances 4 exposed
Issued
Mar 29, 2022
Abate by
Apr 22, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On and/or before February 24, 2022 appliances were plugged into relocatable power taps and not used according to listing and labeling instructions.  Employee(s) were exposed to potential electrical shock and/or fire hazard(s).  In the following location(s): a) Pipe Shop: Black MicroFridge. b) Pipe Shop: Supervisors Office: Black Kenmore Elite Microwave, Brown ABSOCOLD MicroFridge. c) Carpenters Shop: Black Household Microwave  d) Sign Shop: Black ABSOCOLD Microwave, White General Electric Refrigerator
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 5 3 instances 3 exposed
Issued
Mar 29, 2022
Abate by
Apr 22, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less was used for storage:  On and/or before February 24, 2022 the employer permitted materials to be stored directly in front of the electrical panel(s). This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency.  Employee(s) were exposed to the potential of shock and/or fire hazard(s)  In the following locations: a) Pipe Shop Supply Shed  b) Locks Shop c) Metal Shop
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 29, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  Pipe Shop Supply Shed: On and/or before February 24, 2022 employee(s) used outlets to power abrasive blaster equipment. The energized electrical outlet was missing the protective faceplate.  Employee(s) were exposed to electrical shock and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

1910.305 E02

Serious Gravity 5 2 instances 26 exposed
Issued
Mar 29, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.305(e)(2): Switches, circuit breakers and switchboards installed in wet locations were not enclosed in weatherproof enclosures:  On and/or before February 24, 2022 employee(s) have access to eye wash station(s) in the event a foreign object enters the eye. The eyewash stations were in close proximity to live electrical fixtures.  This condition potentially exposed employee(s) to electrical shock hazard(s)  In the following locations:  a) Carpenters shop  b) Electrical Shop
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 2 instances 2 exposed
Issued
Mar 29, 2022
Abate by
Apr 22, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  On and/or before February 24, 2022 employee(s) used the portable extension cord(s) as permanent power to power items such as a television and/or computer/presentation electrical appliances. Employee(s) were exposed to electrical shock and/or fire hazard(s).  In the following Locations:  a) Carpenter Shop  b) Conference Training Room
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 29, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  Metal Shop Exterior: On and/or before February 24, 2022 employee(s) used the green extension cord to power tools and equipment which had the insulation pulled from the terminal joint. Employee(s) were exposed to electrical shock and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

1910.334 A02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 29, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket).  Pipe Shop: On and/or before February 24, 2022 employee(s) used the grinder/buffer to grind down parts and/or tools. The grinders black cord had damage to the jacket/insulation exposing the inner wires. Employee(s) were exposed to electrical shock and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

View MCI West - MCB Camp Pendleton Facilities Maintenance Sustainment Division's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345802524.