Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: RONCEVERTE STORE, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of RONCEVERTE STORE, LLC in 302 FRANKFORD RD, RONCEVERTE, WV 24970 (NAICS 447110). OSHA activity number 345836621.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ronceverte Store, LLC — free Get an email when a new federal OSHA severe-injury report for Ronceverte Store, LLC is published. One employer, no account, unsubscribe in one click.
Site address
302 FRANKFORD RD
City
RONCEVERTE
State
WV
ZIP
24970
Mailing
302 FRANKFORD RD, RONCEVERTE, WV 24970
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
447110
Employees
2
Ownership type
A

9 citations on file for this inspection.

1910.36 D01

Serious Gravity 10 1 instance 1 exposed
Issued
Sep 8, 2022
Abate by
Sep 20, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge.  a)302 Frankford Rd; On or about March 16, 2022, employees are not able to open an exit route door from the inside without the use of a key that is located inside an unused cash register on the counter by the front door.
Recent events (1)
  • — Z (S) $0

1910.37 A03

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 8, 2022
Abate by
Sep 20, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.37(a)(3): Materials or equipment were placed, either permanently or temporarily, within the exit route:  a) 302 Frankford Rd; On or about March 16, 2022, and times prior, a shelf was located in front of the emergency exit door and made it difficult to get to the doorknob.  In addition, the employees place a large rolling cooler in front of the door when moving from the kitchen to the bathroom so they can use the shortest route possible.  In addition, employees work in the store on a daily basis.  A shelf and a rolling cooler were placed within the exit route restricting access to the emergency exit door.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 10 1 instance 1 exposed
Issued
Sep 8, 2022
Abate by
Sep 14, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling.  a) Front Register; On or about March 16, 2022, and times prior, power strips were connected to each other to supply power to each other and the equipment that was plugged into the power strips.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 8, 2022
Abate by
Sep 14, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords were used to run through holes in walls, ceilings, or floors  a) 302 Frankford Rd; On or about March 16, 2022, and times prior, a flexible cord was installed, through a hole in the ceiling, to power LED lights that were placed on the ceiling of the store, to have access to electricity to function.
Recent events (1)
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 10 1 instance 1 exposed
Issued
Sep 8, 2022
Abate by
Sep 20, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:  a) Back wall of Kitchen; On or about March 16, 2022, and times prior, employees were exposed to live parts in an electrical panel that was not closed, covered, or enclosed.  b) Wall next to front register; On or about March 16, 2022, and times prior, employees were exposed to live parts in an electrical panel that was left open.
Recent events (1)
  • — Z (S) $0

1910.305 B03 II

Serious Gravity 10 2 instances 1 exposed
Issued
Sep 8, 2022
Abate by
Sep 20, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.305(b)(3)(ii): Boxes shall be closed by suitable covers securely fastened in place.  a) Back wall of kitchen; On or about March 16, 2022, and times prior, employees worked around electrical boxes that did not have the covers securely fastened in place.  b) Wall by front register; On or about March 16 2022, and times prior, employees worked around an electrical box that was open and unsecured, exposing employees to live electrical components.
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 8, 2022
Abate by
Sep 20, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage:   a) Back wall of Kitchen; On or about March 16, 2022, and times prior, the area underneath multiple electrical panels was used for storage.
Recent events (1)
  • — Z (S) $0

1910.157 E03

Other-than-serious 3 instances 1 exposed
Issued
Sep 8, 2022
Abate by
Sep 27, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:   a) Kitchen; Portable fire extinguishers were not subjected to an annual maintenance check.  b) Front counter; Portable fire extinguishers were not subjected to an annual maintenance check.  c) Back wall next to cooler; Portable fire extinguishers were not subjected to an annual maintenance check.
Recent events (1)
  • — Z (O) $0

1910.157 E02

Other-than-serious 3 instances 1 exposed
Issued
Sep 8, 2022
Abate by
Sep 27, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  a) Back wall near cooler; On or about March 16, 2022 and times prior, portable fire extinguishers were not subjected to monthly visual inspections with the last known inspection conducted in 2017.  b) Kitchen; On or about March 16, 2022 and times prior, portable fire extinguishers were not subjected to monthly visual inspections with the last known inspection conducted in 2017.  c) Floor by front door; On or about March 16, 2022 and times prior, portable fire extinguishers were not subjected to monthly visual inspections with no known inspection being conducted as inspection tag was not on fire extinguisher.
Recent events (1)
  • — Z (O) $0

View Ronceverte Store, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345836621.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.