HOUSTON, TX —
OSHA Inspection: GOWAN MECHANICAL SERVICES INC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of GOWAN MECHANICAL SERVICES INC in 1021 MAIN ST., HOUSTON, TX 77002 (NAICS 238220). OSHA activity number 345873780.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GOWAN MECHANICAL SERVICES INC
- Site address
- 1021 MAIN ST.
- City
- HOUSTON
- State
- TX
- ZIP
- 77002
- Mailing
- 5550 AIRLINE DRIVE, HOUSTON, TX 77076
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238220
- Employees
- 50
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.333 A01
- Issued
- Sep 26, 2022
- Abate by
- Oct 3, 2022
- Penalty
- Initial $10,151 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee worked on or was near to them: a) At the jobsite, a 4160-volt electrical control panel was not deenergized before an employee worked on it, exposing employees to the hazard of electrical shock.
Recent events (2)
- — I (S) $0
- — Z (S) $10151
1910.335 A01 I
- Issued
- Sep 26, 2022
- Abate by
- Oct 3, 2022
- Penalty
- Initial $10,151 · Current $10,151
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees were not wearing protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed when working in an area where there was a potential electrical hazard: a) At the jobsite, employees conducting maintenance work on the 4160-Volt Electrical Control Panel were not wearing fire resistant shirts and pants, full flash suits, hard hats, and arc-rated gloves and leather shoes, exposing the employees to the hazard of electrical shock and burns.
Recent events (2)
- — I (O) $10151
- — Z (S) $10151
1910.335 A01 V
- Issued
- Sep 26, 2022
- Abate by
- Oct 3, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(v):Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face: a) At the Jobsite, employees conducting maintenance work on the 4160-Volt Electrical Control Panel were not wearing face shields and safety glasses, exposing the employees to the hazard of electrical shock and burns.
Recent events (2)
- — I (O) $0
- — Z (S) $0
More inspections at Gowan Mechanical Services INC
View Gowan Mechanical Services INC's full OSHA safety record →
More inspections in this industry (NAICS 238220)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345873780.