Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: IGS INDUSTRIES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of IGS INDUSTRIES, INC. in 200 COUNTRY CLUB ROAD, MEADOW LANDS, PA 15347 (NAICS 339991). OSHA activity number 345874473.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch IGS Industries, INC. — free Get an email when a new federal OSHA severe-injury report for IGS Industries, INC. is published. One employer, no account, unsubscribe in one click.
Site address
200 COUNTRY CLUB ROAD
City
MEADOW LANDS
State
PA
ZIP
15347
Mailing
200 COUNTRY CLUB ROAD, MEADOW LANDS, PA 15347
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
339991
Employees
140
Ownership type
A

4 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 5 1 instance 5 exposed
Issued
Jul 11, 2022
Penalty
Initial $9,324 · Current $4,800 Reduced
29 CFR  1910.303(g)(2)(i):  Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  a) Jobsite, Laser Room, 200 Country Club Road, Meadowlands, PA 15347:  Observed on or about March 23, 2022, live parts of electric equipment contained within a GE A Series Panelboard (480Volt, 3 phase) was not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i).  Some openings on the left and right side of the panelboard were covered by duct tape.  Employees using the panel board were exposed to the hazard of electric shock.
Recent events (2)
  • — I (S) $4800
  • — Z (S) $9324

1910.178 L04 III

Other-than-serious 1 instance 5 exposed
Issued
Jul 11, 2022
Abate by
Aug 4, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not being conducted at least once every three years:   a) Jobsite, 200 Country Club Road, Meadowlands, PA 15347:  On or about March 23, 2022, the employer did not ensure that each employee who operates a powered industrial truck was certified at least once every three years.   Some employees who currently operate powered industrial trucks were not certified within the past three years.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 E01 II

Other-than-serious 1 instance 5 exposed
Issued
Jul 11, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(e)(1)(ii):  Electric equipment was used without markings giving voltage, current, wattage, or other ratings as necessary:  a) Jobsite, Laser Room, 200 Country Club Road, Meadowlands, PA 15347:  Observed on or about March 23, 2022, a GE A Series Panelboard (480 Volt, 3 phase) was not equipped with markings giving the voltage, current, wattage, or other ratings necessary.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV A

Other-than-serious 1 instance 1 exposed
Issued
Jul 11, 2022
Abate by
Aug 4, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   a) Press Room, 200 Country Club Road, Meadowlands, PA 15347:  Observed on or about March 30, 2022, a yellow flexible cord that was plugged into a wall outlet (110 volt) was used as a substitute for the fixed wiring of the structure.  The cord was being used to supply power to a light on a Bliss press marked HI45F.  The cord was draped over pipes and conduits located along the wall and near the ceiling behind the press.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View IGS Industries, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345874473.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.