CRANBERRY, PA —
OSHA Inspection: JOANN
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of JOANN in 6945 U.S. 322, CRANBERRY, PA 16319 (NAICS 451130). OSHA activity number 345881601.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- JOANN
- Site address
- 6945 U.S. 322
- City
- CRANBERRY
- State
- PA
- ZIP
- 16319
- Mailing
- 6945 U.S. 322, CRANBERRY, PA 16319
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 451130
- Employees
- 13
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.305 E01
- Issued
- May 5, 2022
- Abate by
- Jun 1, 2022
- Penalty
- Initial $7,044 · Current $4,931 Reduced
General-duty citation text
29 CFR 1910.305(e)(1):Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures: a) JoAnn; back office area/storage room;- on or about 04/07/2022, and at times prior thereto, water was leaking through the roof and onto a 480/277V electrical panel box. (b) JoAnn; back office area/storage room;- on or about 04/07/2022, and at times prior thereto, water was leaking through the roof and onto a 120/280V electrical panel box. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $4930.8
- — Z (S) $7044
1910.304 F01 VI
- Issued
- May 5, 2022
- Abate by
- Jun 1, 2022
- Penalty
- Initial $5,283 · Current $3,698 Reduced
General-duty citation text
29 CFR 1910.304(f)(1)(vi):Circuit breakers shall clearly indicate whether they are in the open (off) or closed (on) position. a.) JoAnn; back office/storage area - on or about 04/07/2022, and at times prior thereto, masking tape had been placed over individual circuit breakers in the panels. The tape prevented identifying whether the breakers were in the On or Off position. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $3698.1
- — Z (S) $5283
1910.334 B03
- Issued
- May 5, 2022
- Abate by
- Jun 1, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(b)(3):Overcurrent protection modification. Overcurrent protection of circuits and conductors may not be modified, even on a temporary basis, beyond that allowed by 1910.304(e), the installation safety requirements for overcurrent protection. a) JoAnn on or about 04/07/2022, and at times prior thereto, in the back office/storage area: Masking tape was placed on the circuit breakers, modifying the normal function of the breaker to perform properly in case of overcurrent. Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 II
- Issued
- May 5, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) JoAnn; Back office area/storage room- On or about 4/7/2022, and at times prior thereto, the area in front of 480/277V 3 phase electrical panel box was being used for storage. A garbage can was staged in front of two electrical panels. No abatement certification or documentation required