Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of JOANN in 6945 U.S. 322, CRANBERRY, PA 16319 (NAICS 451130). OSHA activity number 345881601.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Joann — free Get an email when a new federal OSHA severe-injury report for Joann is published. One employer, no account, unsubscribe in one click.
Establishment
JOANN
Site address
6945 U.S. 322
City
CRANBERRY
State
PA
ZIP
16319
Mailing
6945 U.S. 322, CRANBERRY, PA 16319
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
451130
Employees
13
Ownership type
A

4 citations on file for this inspection.

1910.305 E01

Serious Gravity 5 1 instance 13 exposed
Issued
May 5, 2022
Abate by
Jun 1, 2022
Penalty
Initial $7,044 · Current $4,931 Reduced
29 CFR  1910.305(e)(1):Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:  a) JoAnn; back office area/storage room;- on or about 04/07/2022, and at times prior thereto, water was leaking through the roof and onto a 480/277V electrical panel box.  (b) JoAnn; back office area/storage room;- on or about 04/07/2022, and at times prior thereto, water was leaking through the roof and onto a 120/280V electrical panel box.   ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $4930.8
  • — Z (S) $7044

1910.304 F01 VI

Serious Gravity 1 2 instances 13 exposed
Issued
May 5, 2022
Abate by
Jun 1, 2022
Penalty
Initial $5,283 · Current $3,698 Reduced
29 CFR  1910.304(f)(1)(vi):Circuit breakers shall clearly indicate whether they are in the open (off) or closed (on) position.   a.) JoAnn; back office/storage area -  on or about 04/07/2022, and at times prior thereto, masking tape had been placed over individual circuit breakers in the panels. The tape prevented identifying whether the breakers were in the On or Off position.  ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $3698.1
  • — Z (S) $5283

1910.334 B03

Serious Gravity 1 1 instance 13 exposed
Issued
May 5, 2022
Abate by
Jun 1, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.334(b)(3):Overcurrent protection modification. Overcurrent protection of circuits and conductors may not be modified, even on a temporary basis, beyond that allowed by 1910.304(e), the installation safety requirements for overcurrent protection.  a) JoAnn on or about 04/07/2022, and at times prior thereto, in the back office/storage area: Masking tape was placed on the circuit breakers, modifying the normal function of the breaker to perform properly in case of overcurrent.  Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 II

Other-than-serious 1 instance 13 exposed
Issued
May 5, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  a) JoAnn; Back office area/storage room- On or about 4/7/2022, and at times prior thereto, the area in front of 480/277V 3 phase electrical panel box was being used for storage. A garbage can was staged in front of two electrical panels.  No abatement certification or documentation required
Recent events (2)
  • — I (O) $0
  • — Z (O) $0