Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: ONWARD BEACH RESORT GUAM, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ONWARD BEACH RESORT GUAM, INC. in 445 GOV CARLOS G CAMACHO RD, TAMUNING, GU 96913 (NAICS 721110). OSHA activity number 345900344.

Watch Onward Beach Resort Guam, INC. — free Get an email when a new federal OSHA severe-injury report for Onward Beach Resort Guam, INC. is published. One employer, no account, unsubscribe in one click.
Site address
445 GOV CARLOS G CAMACHO RD
City
TAMUNING
State
GU
ZIP
96913
Mailing
445 GOV CARLOS G CAMACHO RD, TAMUNING, GU 96913
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
80
Ownership type
A

7 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 1 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $5594.00 · Current $3916.00 Reduced
29 CFR  1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  Basement maintenance area, walkway outside office:  The receptacle outlet near the garden hose was pulled out of the gang box and exposed live electrical contacts.  Employees were exposed to electrical hazards.
Recent events (2)
  • — I (S) $3915.8
  • — Z (S) $5594

1910.303 B02

Serious Gravity 1 2 instances 5 exposed
Issued
Abate by
Penalty
Initial $5594.00 · Current $3916.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) In the My Mart convenience store: A relocatable power tap designed for low amperage applications was used to power a microwave and multiple refrigerators and was plugged in series "daisy chained" with another relocatable power tap. Employees were exposed to electrical and fire hazards.  b) In the maintenance section, basement: A job-made electric lighting pole had an electrical outlet box designed to be installed in the wall mounted to provide power. Employees were exposed to electrical and fire hazards.
Recent events (2)
  • — I (S) $3915.8
  • — Z (S) $5594

1910.305 J01 I

Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located had live parts normally exposed to employee contact:  Basement maintenance area, carpenter's light stand: The receptacle box on the  makeshift light stand was missing a cover.  Employees were exposed to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 A04

Other-than-serious 3 instances 6 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times.   a) Concierge/front desk office/bell staff room:  An overhead exit light was not illuminated as required.  Employees were exposed to egress impediment in the event of a fire.  b) Basement guest game room, leading to guest Laundry Room, over Entrance and leading to Restroom: An overhead exit light was not illuminated as required.  Employees were exposed to egress impediment in the event of a fire.  c) Third floor, near accounting office: An overhead exit light was not illuminated as required.  Employees were exposed to egress impediment in the event of a fire.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 C01

Other-than-serious 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  Basement maintenance exit: There was an unmounted fire extinguisher by the exit from the maintenance department.  Employees were exposed to fire hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.176 C

Other-than-serious 3 instances 6 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.176(c): Storage areas were not kept free from accumulation of materials that constituted hazards from tripping, fire, explosion or pest harborage:  a) Basement maintenance boiler: There were paint cans and several 55-gallon drums of petroleum oil products and other debris stored throughout the work areas.  Employees were exposed to tripping and egress impediment hazards.  b) Old generator room: There were paint cans and several 55-gallon drums of petroleum oil products and other debris stored throughout the work areas.  Employees were exposed to tripping and egress impediment hazards.  c) By Exit area: There were paint cans and several 55-gallon drums of petroleum oil products and other debris stored throughout the work areas.  Employees were exposed to tripping and egress impediment hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 A02 IX

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(a)(2)(ix): Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard:  Basement maintenance area, carpenter's light stand: There was a lamp on the makeshift light stand with the uncovered incandescent bulb exposed to breakage.  Employees were exposed to laceration hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View ONWARD BEACH RESORT GUAM, INC.'s full OSHA safety record →