OSHA Inspection: PTF INSULATION FABRICATORS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PTF INSULATION FABRICATORS in 2407 TEXOMA DRIVE, DENISON, TX 75020 (NAICS 238310). OSHA activity number 345905475.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch PTF Insulation Fabricators — free Get an email when a new federal OSHA severe-injury report for PTF Insulation Fabricators is published. One employer, no account, unsubscribe in one click.
Site address
2407 TEXOMA DRIVE
City
DENISON
State
TX
ZIP
75020
Mailing
2407 TEXOMA DRIVE, DENISON, TX 75020
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238310
Employees
24
Ownership type
A

8 citations on file for this inspection.

1910.147 C01

Serious Gravity 5 1 instance 6 exposed
Issued
May 16, 2022
Abate by
Jun 14, 2022
Penalty
Initial $3,315 · Current $1,989 Reduced
29 CFR  1910.147(c)(1):The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative.  On or about April 12, 2022, and times prior thereto, the employer did not provide an energy control program to their authorized employee performing electrical work on the NGO panel board.  The employee(s) were exposed to electrical hazards.
Recent events (2)
  • — I (S) $1989
  • — Z (S) $3315

1910.212 A03 II

Serious Gravity 5 2 instances 6 exposed
Issued
May 16, 2022
Abate by
Jun 14, 2022
Penalty
Initial $3,315 · Current $1,989 Reduced
29 CFR  1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s).   On or about April 12, 2022, and times prior thereto, two double diagonal vertical band saws were used without the unused portion of the blades not guarded exposing employees to amputation hazards.  a) Vertical double blade band saw number 23 was operation with 19 inches of the blade not guarded,  b) Vertical double blade band saw number 24, was in operation with 19 inches of the blade not guarded.
Recent events (2)
  • — I (S) $1989
  • — Z (S) $3315

1910.219 D01

Serious Gravity 1 1 instance 6 exposed
Issued
May 16, 2022
Penalty
Initial $2,113 · Current $1,268 Reduced
29 CFR  1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o).   On or about April 12, 2022, and times prior thereto, at the 90s machine, the employer did not ensure the pulley of the Baldor motor was guarded exposing employees to rotating pulley.
Recent events (2)
  • — I (S) $1267.8
  • — Z (S) $2113

1910.219 E03 I

Serious Gravity 1 1 instance 6 exposed
Issued
May 16, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.219(e)(3)(i): Vertical or inclined belt(s) were not enclosed by guard(s) conforming to the requirements specified at 29 CFR 1910.219(m) and (o)(a).  On or about April 12, 2022, and times prior thereto, at the 90s machine, the employer did not provide a guard to protect machine operator(s) from rotating parts, exposing employee(s) to caught-by hazard(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 B02 IV B

Serious Gravity 1 1 instance 1 exposed
Issued
May 16, 2022
Abate by
Jun 14, 2022
Penalty
Initial $2,486 · Current $1,492 Reduced
29 CFR  1910.333(b)(2)(iv)(B):Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that(a).  On or about April 12, 2022,  and times prior thereto. the employer did not ensure qualified employees tested circuits and electrical parts to ensure they were de-energized prior to installing electrical time clock to electrical panel exposing the employee to electrical hazards.
Recent events (2)
  • — I (S) $1491.6
  • — Z (S) $2486

1910.304 F01 VIII

Other-than-serious 1 instance 6 exposed
Issued
May 16, 2022
Abate by
Jun 14, 2022
Penalty
Initial $465 · Current $279 Reduced
29 CFR  1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD."  On or about April 12, 2022, and times prior thereto, in the production building, west side wall, the employer allowed employees to turn fluorescent lights on and off from the electrical panel box and circuits that were not listed and marked "SWD", exposing employees to electrical shock hazards.
Recent events (2)
  • — I (O) $279
  • — Z (O) $465

1910.305 B01 II

Other-than-serious 1 instance 1 exposed
Issued
May 16, 2022
Penalty
Initial $395 · Current $237 Reduced
29 CFR  1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   On or about April 12, 2022, and times prior thereto, power box for the Baldor motor power source missing knock-out plugs exposing employees to electrical shock hazards.
Recent events (2)
  • — I (O) $237
  • — Z (O) $395

1910.305 B02 I

Other-than-serious 1 instance 1 exposed
Issued
May 16, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:   On or about April 12, 2022, and times prior thereto, in the PVC room, north side wall, heater panel box with live wires, missing cover plate exposing employees to electrical shock hazards.