MIAMI GARDENS, FL —
OSHA Inspection: C DAVIS ELECTRIC CO., INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of C DAVIS ELECTRIC CO., INC. in 347 DON SHULA DRIVE, MIAMI GARDENS, FL 33056 (NAICS 811219). OSHA activity number 345928972.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- C DAVIS ELECTRIC CO., INC.
- Site address
- 347 DON SHULA DRIVE
- City
- MIAMI GARDENS
- State
- FL
- ZIP
- 33056
- Mailing
- 1701 SW 100TH TERRACE, MIRAMAR, FL 33025
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811219
- Employees
- 18
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.403 I01 I
- Issued
- Oct 27, 2022
- Abate by
- Nov 23, 2022
- Penalty
- Initial $13,052 · Current $6,751 Reduced
General-duty citation text
29 CFR 1926.403(i)(1)(i): The dimension of the working space in the direction of access to live parts operating at 600 volts, nominal, or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than that 30 inches: On or about 04/29/2022, on the Hard Rock Stadium red bull area located at 347 Don Shula Drive , Miami Gardens, Florida, employees were exposed to electric arc flash hazards while accessing/manipulating an energized meter socket box without taking the required exposure control and/or mitigation measures. IN THE ALTERNATIVE: 29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means: On or about 04/29/2022, on the Hard Rock Stadium red bull area located at 347 Don Shula Drive , Miami Gardens, Florida, employees were exposed to electric arc flash hazards while accessing/manipulating an energized meter socket box without taking the required exposure control and/or mitigation measures.
Recent events (2)
- — I (S) $6751
- — Z (S) $13052
1926.95 A
- Issued
- Oct 27, 2022
- Abate by
- Nov 23, 2022
- Penalty
- Initial $13,052 · Current $6,751 Reduced
General-duty citation text
29 CFR 1926.95(a): Personal protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, was not provided, used, or maintained in a sanitary and reliable condition it was necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation, or physical contact: On or about 04/29/2022, on the Hard Rock Stadium red bull area located at 347 Don Shula Drive , Miami Gardens, Florida, employees were exposed to electric and arc flash hazards while approaching/removing a plastic cover from an energized 600V meter socket box and not wearing the proper personal protection equipment.
Recent events (2)
- — I (S) $6751
- — Z (S) $13052
1926.20 B01
- Issued
- Oct 27, 2022
- Abate by
- Nov 23, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.20(b)(1): The employer did not initiate and maintain such programs as may be necessary to comply with this part: On or about 04/29/2022, on the Hard Rock Stadium red bull area located at 347 Don Shula Drive, Miami Gardens, Florida, employees were exposed to electric arc flash hazards when engaging in the practice of direct contact with an energized meter socket box.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at C Davis Electric CO., INC.
View C Davis Electric CO., INC.'s full OSHA safety record →
More inspections in this industry (NAICS 811219)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345928972.