OSHA Inspection: SOCIAL SECURITY ADMINISTRATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SOCIAL SECURITY ADMINISTRATION in 8000 NISKY CENTER, SUITE 14, CHARLOTTE AMALIE, VI 00802 (NAICS 923130). OSHA activity number 345932933.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Social Security Administration — free Get an email when a new federal OSHA severe-injury report for Social Security Administration is published. One employer, no account, unsubscribe in one click.
Site address
8000 NISKY CENTER, SUITE 14
City
CHARLOTTE AMALIE
State
VI
ZIP
00802
Mailing
8000 NISKY CENTER, SUITE 14, CHARLOTTE AMALIE, VI 00802
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
923130
Employees
5
Ownership type
D

2 citations on file for this inspection.

1910.157 C01

Other-than-serious 1 instance 5 exposed
Issued
Sep 30, 2022
Abate by
Oct 17, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.157(c)(1): Portable fire extinguisher was not readily accessible to employees without subjecting the employees to possible injuries:  a. On or about 3 May 2022, 8000 Nisky Center, Ste. 14, at the Classroom, a fire extinguisher was blocked by a printer mounted on a table, exposing employees to fire hazards.
Recent events (1)
  • — Z (O) $0

1910.303 G01

Other-than-serious 2 instances 5 exposed
Issued
Sep 30, 2022
Abate by
Oct 17, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  a. On or about 3 May 2022, 8000 Nisky Center, Ste. 14, at the Computer Room, an electrical panel (RP-G 120/208 Y 3PH 4W FED from SSA MBP) was not provided and maintained with a minimum of 3 feet working clearance, exposing employees to electrical hazards.  b. On or about 3 May 2022, 8000 Nisky Center, Ste. 14, at the Training Classroom, an electrical panel (RP-E 120/208 Y 3PH 4W FED from SSA MBP) was not provided and maintained with a minimum of 3 feet working clearance, exposing employees to electrical hazards.
Recent events (1)
  • — Z (O) $0

View Social Security Administration's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345932933.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.