JERSEY CITY, NJ —
OSHA Inspection: U.S. POSTAL SERVICE
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of U.S. POSTAL SERVICE in 80 COUNTY ROAD, JERSEY CITY, NJ 07097 (NAICS 491110). OSHA activity number 345979611.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. POSTAL SERVICE
- Site address
- 80 COUNTY ROAD
- City
- JERSEY CITY
- State
- NJ
- ZIP
- 07097
- Mailing
- 80 COUNTY ROAD, JERSEY CITY, NJ 07097
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 491110
- Employees
- 2002
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.37 A03
- Issued
- Nov 23, 2022
- Penalty
- Initial $9,116 · Current $6,000 Reduced
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed. No materials or equipment may be placed, either permanently or temporarily, within the exit route: Location: Warehouse Employees were exposed to blocked exit routes preventing quick access to the emergency exit in the event of a fire or emergency. Instance A: By exit door EDF 15, a pallet jack was placed along the exit route preventing quick access to the emergency exit during an event of a fire or emergency. Instance B At the compacting room exit door EDF-21, a mail cart is placed along the exit route preventing quick access to the emergency exit during an event of a fire or emergency. Violation observed 05/24/2022
Recent events (3)
- — F (S) $6000
- — C (S) $9116
- — Z (S) $9116
1910.303 G01
- Issued
- Nov 23, 2022
- Penalty
- Initial $9,116 · Current $6,000 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Location: Cafeteria, Battery room, Column 24E, and Column 24G Instance A : At the cafeteria, a soda vending machine was placed at the front of an electrical Panel (480 Volts) Instance B: At the Battery charging room, items such as but not limited to forklift parts were stored at the front of an electrical panel. Instance C: By Column 24E, mail carts were stored at the front of an electrical panel (480 Volt) Instance D: By Column 24G, items such as but not limited to cardboard and mail carts were stored at the front of an electrical panel. Violation observed 05/24/2022
Recent events (3)
- — F (O) $6000
- — C (S) $9116
- — Z (S) $9116
1910.305 B02 I
- Issued
- Nov 23, 2022
- Abate by
- Dec 6, 2022
- Penalty
- Initial $9,116 · Current $5,009 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, outlet boxes and fittings were not provided with covers approved for the purpose; and each fitting in completed installations did not have a cover, faceplate, or fixture canopy: Location: Gate 19 An electrical panel missing front cover exposing employees to electrical hazard. Violation observed 05/24/2022
Recent events (3)
- — F (S) $5008.8
- — C (S) $9116
- — Z (S) $9116
1910.157 C01
- Issued
- Nov 23, 2022
- Penalty
- Initial $1,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: Location: Compactor room At the compacting room, items such as garbage can and carboard at stored at the front of an extinguisher impeding access to the extinguisher. Violation observed on 05/24/2022
Recent events (3)
- — F (O) $0
- — C (O) $1000
- — Z (O) $1000
More inspections at U.S. Postal Service
View U.S. Postal Service's full OSHA safety record →
More inspections in this industry (NAICS 491110)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345979611.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.