ANNISTON, AL —
OSHA Inspection: UNITED STATES DEPARTMENT OF THE ARMY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of UNITED STATES DEPARTMENT OF THE ARMY in ANNISTON ARMY DEPOT. BLDG 95, ANNISTON, AL 36201 (NAICS 336992). OSHA activity number 346085384.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- UNITED STATES DEPARTMENT OF THE ARMY
- Site address
- ANNISTON ARMY DEPOT. BLDG 95
- City
- ANNISTON
- State
- AL
- ZIP
- 36201
- Mailing
- 7 FRANKFORD AVE. BLDG 1, ANNISTON, AL 36201
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336992
- Employees
- 2623
- Ownership type
- D
Citations
6 citations on file for this inspection.
1910.269 A02 IV
- Issued
- Dec 8, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(a)(2)(iv): The employer did not determine that each employee is complying with all required safety related work practices by regular supervision and Annual inspections: (a) On or about 7/11/2022 and at times prior to, Aniston Army Depot, employees exposed to contact with 7,200 VAC electrical current during the performance of electrical work were not supervised and inspected annually as required.
Recent events (1)
- — Z (S) $0
1910.269 C01 II
- Issued
- Dec 8, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(c)(1)(ii): The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (c)(2) though (c)(4) of this section with the employees involved before they start each job: (a) On or about 7/11/2022 and at times prior to, Aniston Army Depot, employees were exposed to contact with 7,200 VAC when performing electrical work and an adequate job briefing was not performed that covered hazards associated with the job, work procedures involved, special precautions, energy-source controls, and personal protective equipment required.
Recent events (1)
- — Z (S) $0
1910.269 J02 III
- Issued
- Dec 8, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(j)(2)(iii): Live-line tools used for primary employee protection shall be removed from service every 2 years, and whenever required under paragraph (j)(2)(ii) of this section, for examination, cleaning, repair, and testing: (a) On or about 7/11/2022 and at times prior to, Aniston Army Depot, employees were exposed to electrical hazards when performing work utilizing live line tools that were not adequately tested as required when opening cutout switches energized at 7,200 VAC.
Recent events (1)
- — Z (S) $0
1910.269 L03 III
- Issued
- Dec 8, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(l)(3)(iii): The employer did not ensure that no employee approached or took any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless provisions described in (l) (3) (iii) (A) - (C) were followed: (a) On or about 7/11/2022 and at times prior to, Aniston Army Depot, employees were exposed to contact with 7,200 VAC electrical current when performing electrical work and utilizing tools such as the Lineman's Insulated 4 in 1 Box Wrench, Model KT223X4-INS, within nine (9) inches of an energized Hubbell cutout switch, Model C710112PB.
Recent events (1)
- — Z (S) $0
1910.269 M03 I
- Issued
- Dec 8, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(m)(3)(i): The employee that the employer designates pursuant to paragraph (m)(2) of this section as being in charge of the clearance shall make a request of the system operator to deenergize the particular section of line or equipment. The designated employee becomes the employee in charge (as this term is used in paragraph (m)(3) of this section) and is responsible for the clearance: (a) On or about 7/11/2022 and at times prior to, Aniston Army Depot, employees were exposed to contact with 7,200 VAC and the necessary steps were not taken to deenergize power pole switches.
Recent events (1)
- — Z (S) $0
1910.269 P04 II
- Issued
- Dec 8, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(p)(4)(ii): A designated employee other than the equipment operator shall observe the approach distance to exposed lines and equipment and provide timely warnings before the minimum approach distance required by paragraph (p)(4)(i) of this section is reached, unless the employer can demonstrate that the operator can accurately determine that the minimum approach distance is being maintained: (a) On or about 7/11/2022 and at times prior to, Aniston Army Depot, employees were exposed to contact with electrical hazards and a designated employee was not present when a lineman was elevated in a bucket truck while working near 7,200 VAC distribution lines.
Recent events (1)
- — Z (S) $0
More inspections at United States Department of the Army
View United States Department of the Army's full OSHA safety record →
More inspections in this industry (NAICS 336992)
More inspections in AL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346085384.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.