Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: UNITED STATES DEPARTMENT OF THE ARMY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of UNITED STATES DEPARTMENT OF THE ARMY in ANNISTON ARMY DEPOT. BLDG 95, ANNISTON, AL 36201 (NAICS 336992). OSHA activity number 346085384.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch United States Department of the Army — free Get an email when a new federal OSHA severe-injury report for United States Department of the Army is published. One employer, no account, unsubscribe in one click.
Site address
ANNISTON ARMY DEPOT. BLDG 95
City
ANNISTON
State
AL
ZIP
36201
Mailing
7 FRANKFORD AVE. BLDG 1, ANNISTON, AL 36201
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336992
Employees
2623
Ownership type
D

6 citations on file for this inspection.

1910.269 A02 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Dec 8, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.269(a)(2)(iv): The employer did not determine that each employee is complying with all required safety related work practices by regular supervision and Annual inspections:   (a) On or about 7/11/2022 and at times prior to, Aniston Army Depot, employees exposed to contact with 7,200 VAC electrical current during the performance of electrical work were not supervised and inspected annually as required.
Recent events (1)
  • — Z (S) $0

1910.269 C01 II

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 8, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.269(c)(1)(ii): The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (c)(2) though (c)(4) of this section with the employees involved before they start each job:  (a) On or about 7/11/2022 and at times prior to, Aniston Army Depot, employees were exposed to contact with 7,200 VAC when performing electrical work and an adequate job briefing was not performed that covered hazards associated with the job, work procedures involved, special precautions, energy-source controls, and personal protective equipment required.
Recent events (1)
  • — Z (S) $0

1910.269 J02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Dec 8, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.269(j)(2)(iii): Live-line tools used for primary employee protection shall be removed from service every 2 years, and whenever required under paragraph (j)(2)(ii) of this section, for examination, cleaning, repair, and testing:  (a) On or about 7/11/2022 and at times prior to, Aniston Army Depot, employees were exposed to electrical hazards when performing work utilizing live line tools that were not adequately tested as required when opening cutout switches energized at 7,200 VAC.
Recent events (1)
  • — Z (S) $0

1910.269 L03 III

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 8, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.269(l)(3)(iii): The employer did not ensure that no employee approached or took any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless provisions described in (l) (3) (iii) (A) - (C) were followed:    (a) On or about 7/11/2022 and at times prior to, Aniston Army Depot, employees were exposed to contact with 7,200 VAC electrical current when performing electrical work and utilizing tools such as the Lineman's Insulated 4 in 1 Box Wrench, Model KT223X4-INS, within nine (9) inches of an energized Hubbell cutout switch, Model C710112PB.
Recent events (1)
  • — Z (S) $0

1910.269 M03 I

Serious Gravity 5 1 instance 2 exposed
Issued
Dec 8, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.269(m)(3)(i): The employee that the employer designates pursuant to paragraph (m)(2) of this section as being in charge of the clearance shall make a request of the system operator to deenergize the particular section of line or equipment. The designated employee becomes the employee in charge (as this term is used in paragraph (m)(3) of this section) and is responsible for the clearance:   (a) On or about 7/11/2022 and at times prior to, Aniston Army Depot, employees were exposed to contact with 7,200 VAC and the necessary steps were not taken to deenergize power pole switches.
Recent events (1)
  • — Z (S) $0

1910.269 P04 II

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 8, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.269(p)(4)(ii): A designated employee other than the equipment operator shall observe the approach distance to exposed lines and equipment and provide timely warnings before the minimum approach distance required by paragraph (p)(4)(i) of this section is reached, unless the employer can demonstrate that the operator can accurately determine that the minimum approach distance is being maintained:   (a) On or about 7/11/2022 and at times prior to, Aniston Army Depot, employees were exposed to contact with electrical hazards and a designated employee was not present when a lineman was elevated in a bucket truck while working near 7,200 VAC distribution lines.
Recent events (1)