Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: APS GRUPA LLC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of APS GRUPA LLC in 10459 S. MUSKEGON AVENUE, CHICAGO, IL 60617 (NAICS 325411). OSHA activity number 346143449.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch APS Grupa LLC — free Get an email when a new federal OSHA severe-injury report for APS Grupa LLC is published. One employer, no account, unsubscribe in one click.
Establishment
APS GRUPA LLC
Site address
10459 S. MUSKEGON AVENUE
City
CHICAGO
State
IL
ZIP
60617
Mailing
10459 S. MUSKEGON AVENUE, CHICAGO, IL 60617
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325411
Employees
120
Ownership type
A

3 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 3 exposed
Issued
Jan 24, 2023
Abate by
Nov 15, 2023
Penalty
Initial $10,046 · Current $5,200 Reduced

Hazardous substances M102

Section (5)(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to combustible agricultural ingredient dust explosion, and deflagration hazards while working near or upstream of an unprotected outdoor dust collector:  a) On or about August 12, 2022, the United Air Specialists, Inc. model FJHI6-8-H filter media dust collector servicing the Silo Building collected combustible agricultural ingredient dusts from upstream bagging operations. The outdoor dust collector lacked means of (1) explosion protection and (2) deflagration propagation protection (isolation) for the upstream processed via the dirty air inlet ducting, the area beneath the dust collector via the material hopper discharge, and the area to the side of the dust collector via the clean air exhaust duct.
Recent events (5)
  • — P (S) $5200
  • — P (S) $5200
  • — P (S) $5200

1910.22 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Jan 24, 2023
Abate by
Apr 3, 2023
Penalty
Initial $10,046 · Current $5,200 Reduced

Hazardous substances M102

29 CFR  1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces were kept in a clean, orderly, and sanitary condition.  a) On or about October 26, 2022, in the Silo Building, the employer did not ensure that floors and elevated non-floor surfaces were maintained in a clean and orderly condition. Combustible agriculture ingredient dust  was allowed to accumulate on equipment and floors exposing employees to potential fire, deflagration, and explosion hazards.
Recent events (2)
  • — I (S) $5200
  • — Z (S) $10046

1910.307 C

Serious Gravity 5 1 instance 1 exposed
Issued
Jan 24, 2023
Abate by
Jul 20, 2023
Penalty
Initial $10,046 · Current $5,100 Reduced

Hazardous substances E101M102

29 CFR  1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:  a.  On or about August 12, 2022,  in the silo building packaging area, employees were exposed to hazards of burns and impact from pressure wave (shock) and/or projectile fragmentation when the electrical wiring utilized in the bagging station(s) were not rated for use in a Class II location.  Ordinary wiring such as,  but not limited to, ordinary extension cords were in use during bagging operations and were not rated for use in a Class II area.
Recent events (4)
  • — P (S) $5100
  • — P (S) $5100
  • — I (S) $5100

View APS Grupa LLC's full OSHA safety record →