Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. FISH AND WILDLIFE SERVICE BILLY FRANK JR. NISQUALLY NATIONAL WILDLIFE REFUGE

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of U.S. FISH AND WILDLIFE SERVICE BILLY FRANK JR. NISQUALLY NATIONAL WILDLIFE REFUGE in 100 BROWN FARM ROAD NE, OLYMPIA, WA 98516 (NAICS 924120). OSHA activity number 346169253.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Fish and Wildlife Service Billy Frank JR. Nisqually National Wildlife Refuge — free Get an email when a new federal OSHA severe-injury report for U.S. Fish and Wildlife Service Billy Frank JR. Nisqually National Wildlife Refuge is published. One employer, no account, unsubscribe in one click.
Site address
100 BROWN FARM ROAD NE
City
OLYMPIA
State
WA
ZIP
98516
Mailing
100 BROWN FARM ROAD NE, OLYMPIA, WA 98516
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
6
Ownership type
D

5 citations on file for this inspection.

1910.29 B13 I

Serious Gravity 5 2 instances 6 exposed
Issued
Oct 5, 2022
Abate by
Nov 23, 2022
Penalty
Initial $0 · Current $0
1910.29(b)(13)(i): The guardrail system opening used around holes that serve as points of access (such as ladderways),  did not have a self-closing gate that slides or swings away from the hole, and was equipped with a top rail and midrail or equivalent intermediate member that met the requirements in paragraph (b) of this section:  a) Facility, where openings at the access point of the Lapeyre alternating tread stairs not equipped with self-closing gates included:  1. Visitor Center East Mechanical Room, exposing employees to a fall of approximately 10-12 feet to the lower level.  2. Administrative Building second floor storage room, exposing employees to a fall of approximately 10-12 feet to the lower level.
Recent events (1)
  • — Z (S) $0

1910.147 C04 I

Serious Gravity 1 1 instance 6 exposed
Issued
Oct 5, 2022
Abate by
Nov 23, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:  a) Maintenance Department, written procedures had not been developed for tasks including:  1. Where the employer utilized the lockout tagout program for safe electrical work practices no written procedures had been developed for repairing and or installing outlets.  2. Written procedures had not been developed where employees performed preventative maintenance and repairs on gasoline and diesel operated equipment, including but not limited to, John Deere riding mower, John Deere 6430 Agricultural tractor, CAT backhoe, Yale forklift, and the dump truck.
Recent events (1)
  • — Z (S) $0

1910.36 G02

Other-than-serious 1 instance 6 exposed
Issued
Oct 5, 2022
Abate by
Nov 23, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:  a) Visitor Center Storage Room 106, where shelving and items stored on the floor reduced the width of the aisle way to 17 inches.
Recent events (1)
  • — Z (O) $0

1910.37 B02

Other-than-serious 1 instance 6 exposed
Issued
Oct 5, 2022
Abate by
Nov 23, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  a) Visitor Center Auditorium, where the designated emergency exit discharge door was not equipped with an exit sign.
Recent events (1)
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 6 exposed
Issued
Oct 5, 2022
Abate by
Nov 23, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:   a) Visitor Center Storage Room 106, where items including a box, shelving and a step stool were stored in front of circuit panel C.
Recent events (1)
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346169253.