OSHA Inspection: US ENGINEERING SERVICES

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of US ENGINEERING SERVICES in 6801 HOLMES RD, KANSAS CITY, MO 64131 (NAICS 333415). OSHA activity number 346170038.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch US Engineering Services — free Get an email when a new federal OSHA severe-injury report for US Engineering Services is published. One employer, no account, unsubscribe in one click.
Site address
6801 HOLMES RD
City
KANSAS CITY
State
MO
ZIP
64131
Mailing
3433 ROANOKE ROAD, KANSAS CITY, MO 64111
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333415
Employees
200
Ownership type
A

8 citations on file for this inspection.

1910.335 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 2, 2024
Abate by
Nov 4, 2024
Penalty
Initial $16,131 · Current $16,131
29 CFR 1910.335(a)(1)(i):  Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  The employer is failing to protect employees from electrical shock hazards associated with servicing energized equipment. This was most recently documented on August 24, 2022. At a U.S. Engineering Services jobsite located at 6801 Holmes Rd, Kansas City, Missouri. Where the employer has an employee exposed to shock, burns and electrocution hazards while servicing the AHU-1 HVAC equipment as a result of the employer?s failure to ensure employees utilize the required electrical PPE for the employee?s hands.
Recent events (3)
  • — F (S) $16131
  • — Z (S) $16131
  • — C (S) $16131

1910.335 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Jul 9, 2024
Abate by
Nov 4, 2024
Penalty
Initial $16,131 · Current $16,131
29 CFR  1910.335(a)(1)(i):Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  The employer is failing to protect employees from electrical shock hazards associated with servicing energized equipment. This was most recently documented on August 24, 2022. At a U.S. Engineering Services jobsite located at 6801 Holmes Rd, Kansas City, Missouri. Where the employer has an employee exposed to shock, burns and electrocution hazards while servicing the AHU-1 HVAC equipment as a result of the employer's failure to ensure employees utilize the required electrical PPE for the employee's hands.
Recent events (3)
  • — F (S) $16131
  • — Z (S) $16131
  • — C (S) $16131

1910.303 B01 IV

Serious Gravity 5 1 instance 1 exposed
Issued
Jan 13, 2023
Abate by
Nov 4, 2024
Penalty
Initial $9,116 · Current $16,131
29 CFR 1910.303(b)(1)(iv):  Electric equipment was not free from recognized hazards that were likely to cause serious physical harm to employees, such as damaged electrical insulation:   The employer is failing to protect employees from electrical shock hazards associated with energized equipment. This was most recently documented on August 24, 2022. At a U.S. Engineering Services jobsite located at 6801 Holmes Rd, Kansas City, Missouri. An employee was exposed to serious injuries due to electrical shock, fire, or burns in that an electrical extension cord repaired with a Legrand Pass and Seymour 15 Amp 125-volt yellow straight blade connector, used to power the Dayton brand wet/dry vac Model 3VE21 was found to be in disrepair with damaged outer insulation, abrasions, and exposed inner wires covered with black electrical tape.
Recent events (3)
  • — F (S) $16131
  • — C (S) $9116
  • — Z (S) $9116

1910.333 B02 I

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Jan 13, 2023
Abate by
Nov 4, 2024
Penalty
Initial $14,502 · Current $16,131
29 CFR 1910.333(b)(2)(i):  The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives:  The employer is failing to protect employees from electrical shock hazards associated with servicing energized equipment. This was most recently documented on August 24, 2022. At a U.S. Engineering Services jobsite located at 6801 Holmes Rd, Kansas City, Missouri. Where the employer has an employee exposed to shock, burns and electrocution hazards from stored energy when servicing the AHU-1 HVAC equipment without having developed and implemented a written procedure.
Recent events (3)
  • — F (O) $16131
  • — C (S) $14502
  • — Z (S) $14502

1910.335 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Jan 13, 2023
Abate by
Nov 4, 2024
Penalty
Initial $14,502 · Current $16,131
29 CFR 1910.335(a)(1)(i):  Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  The employer is failing to protect employees from electrical shock hazards associated with servicing energized equipment. This was most recently documented on August 24, 2022. At a U.S. Engineering Services jobsite located at 6801 Holmes Rd, Kansas City, Missouri. Where the employer has an employee exposed to shock, burns and electrocution hazards while servicing the AHU-1 HVAC equipment as a result of the employer's failure to ensure employees utilize the required electrical PPE for the employee?s eyes and face.
Recent events (3)
  • — F (S) $16131
  • — C (S) $14502
  • — Z (S) $14502

1910.132 D02

Deleted Repeat Gravity 10 1 instance 1 exposed
Issued
Jan 13, 2023
Abate by
Feb 21, 2023
Penalty
Initial $79,761 · Current $0 Reduced
29 CFR 1910.132(d)(2): The employer did not verify, through a written certification, that the required workplace hazard assessment had been performed through a written certification that identifies the workplace evaluated; the person certifying that the evaluation has been performed; the date(s) of the hazard assessment; and, which identifies the document as a certification of hazard assessment.   The employer is failing to protect employees from electrical shock hazards associated with energized equipment. This was most recently documented on August 24, 2022. At a U.S. Engineering Services jobsite located at 6801 Holmes Rd, Kansas City, Missouri. Employees were exposed to serious electrical hazards in that a written hazard assessment certification had not been completed to certify the PPE needs and requirements for the contracted sites, where field employees provide HVAC services.  US Engineering Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard, which was contained in OSHA inspection number 1541625, citation number 1, item number 1 and was affirmed as a final order on 11-19-2021, with respect to a workplace located at 801 E. Douglas Avenue, Wichita, Kansas.
Recent events (3)
  • — F (R) $0
  • — C (R) $79761
  • — Z (R) $79761

1910.333 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Jan 13, 2023
Abate by
Nov 4, 2024
Penalty
Initial $79,761 · Current $16,131 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed shall be deenergized before the employee works on or near them.  The employer is failing to protect employees from electrical shock hazards associated with maintaining equipment with energized parts. This was most recently documented on August 24, 2022. At a U.S. Engineering Services jobsite located at 6801 Holmes Rd, Kansas City, Missouri. The employer did not ensure that employees were deenergizing electrical hazards that were observed during field work on contracted scheduled maintenance and service calls. The employer is failing to protect employees from electrical shock hazards associated with energized equipment. This was most recently documented on August 24, 2022. At a U.S. Engineering Services jobsite located at 6801 Holmes Rd, Kansas City, Missouri. The employer did not ensure that employees were deenergizing electrical hazards that were observed during field work on contracted scheduled maintenance and service calls.  US Engineering Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard, which was contained in OSHA inspection number 1541625, citation number 1, item number 2 and was affirmed as a final order on 11-19-2021, with respect to a workplace located at 801 E. Douglas Avenue, Wichita, Kansas.
Recent events (3)
  • — F (S) $16131
  • — C (R) $79761
  • — Z (R) $79761

1910.333 B02

Serious Gravity 10 1 instance 1 exposed
Issued
Jan 13, 2023
Abate by
Nov 4, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2):    While any employee is exposed to contact with parts of fixed electric equipment or circuits which have been deenergized, the circuits energizing the parts shall be locked out or tagged or both in accordance with the requirements of this paragraph.    The employer is failing to protect employees from electrical shock hazards associated with energized equipment. This was most recently documented on August 24, 2022. At a U.S. Engineering Services jobsite located at 6801 Holmes Rd, Kansas City, Missouri.  Where the employer has an employee exposed to shock, burns and electrocution hazards from stored energy while servicing equipment.   US Engineering Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard, which was contained in OSHA inspection number 1541625, citation number 1, item number 2 and was affirmed as a final order on 11-19-2021, with respect to a workplace located at 801 E. Douglas Avenue, Wichita, Kansas.
Recent events (3)
  • — F (S) $0
  • — C (R) $0
  • — Z (R) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346170038.