Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: H.C. BLAKE CO., INC.

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of H.C. BLAKE CO., INC. in 6125 UNIVERSITY DRIVE, HUNTSVILLE, AL 35806 (NAICS 238220). OSHA activity number 346204662.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch H.C. Blake CO., INC. — free Get an email when a new federal OSHA severe-injury report for H.C. Blake CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
6125 UNIVERSITY DRIVE
City
HUNTSVILLE
State
AL
ZIP
35806
Mailing
2007 N MEMORIAL PARKWAY, SUITE A ATTN: JIM BATSON, HUNTSVILLE, AL 35810
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238220
Employees
1
Ownership type
A

5 citations on file for this inspection.

1910.132 D01 I

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Mar 6, 2023
Abate by
Mar 28, 2024
Penalty
Initial $10,938 · Current $3,230 Reduced
29 CFR 1910.132(d)(1)(i): The employer did not select and have each affected employee use, the types of personal protective equipment that would protect the affected employee(s) from the hazards identified in the hazard assessment:  (a) On or about 09/07/2022, 6125 University Drive, Huntsville, AL 35806, NE Section inside the building, employees working on a live 3 phase 480-volt circuit supplying a HVAC were exposed electrocution hazards because the employer did not have each affected employee use the types of PPE identified by the employer that protected the affected employee from the hazards associated with working on live electrical circuits.
Recent events (3)
  • — F (O) $3230.4
  • — C (S) $10938
  • — Z (S) $10938

1910.132 D02

Other-than-serious Gravity 5 1 instance 1 exposed
Issued
Mar 6, 2023
Abate by
Mar 28, 2024
Penalty
Initial $7,813 · Current $3,229 Reduced
29 CFR  1910.132(d)(2):The employer did not verify that the required workplace hazard assessment has been performed through a written certification that identifies the workplace evaluated, the person certifying that the evaluation has been performed, the date(s) of the hazard assessment, and, which identifies the document as a certification of hazard assessment:  (a) On or about 09/07/2022, 6125 University Dr., Huntsville, AL 35806, throughout the facility, employees, testing, electrical circuits, to determine those which function, those which were mislabeled, and /or those which were dead-ended, or were exposed to electrical hazards from 208 volt and other voltages because the employer had not conducted, evaluated or certified the hazard assessment, regarding electrical hazards within the facility while conducting such testing.
Recent events (3)
  • — F (O) $3229
  • — C (S) $7813
  • — Z (S) $7813

1910.333 A02

Serious Gravity 10 1 instance 1 exposed
Issued
Mar 6, 2023
Abate by
Mar 28, 2024
Penalty
Initial $15,625 · Current $15,625
29 CFR 1910.333(a)(2): Where exposed live parts were not deenergized, work practices that were used were not suitable for the conditions under which the work was performed:  (a) On or about 09/07/2022, 6125 University Drive, Huntsville, AL 35806, NE Section inside the building, employees working on a live 3 phase 480-volt circuit supplying a HVAC were exposed to electrocution hazards because the employer did not ensure that the work practices used were suitable for the conditions under which the work was to be performed and for the voltage level of the exposed electric conductors or circuit parts.
Recent events (3)
  • — F (S) $15625
  • — C (S) $15625
  • — Z (S) $15625

1910.333 C02

Serious Gravity 10 1 instance 1 exposed
Issued
Mar 6, 2023
Abate by
Mar 28, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.333(c)(2): The employer did not ensure that only qualified persons were working on energized circuits and that qualified persons were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools:  (a) On or about 09/07/2022, 6125 University Drive, Huntsville, AL 35806, NE Section inside the building, employees working on a live 3 phase 480-volt circuit supplying a HVAC were exposed to electrocution hazards because the employer did not ensure such persons were capable of working safely on energized circuits and were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.303 F01

Other-than-serious Gravity 5 1 instance 1 exposed
Issued
Mar 6, 2023
Abate by
Mar 28, 2024
Penalty
Initial $7,813 · Current $3,229 Reduced
29 CFR 1910.303(f)(1): Each disconnecting means required by Subpart S of Part 1910 for motors and appliances was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  (a) On or about 09/07/2022, 6125 University Dr., Huntsville, AL 35806, throughout the facility, employees, testing electrical circuits to determine those which were functional or not, and/or those to which equipment was connected, were exposed to electrocution hazards from 208 volt, and other voltages because the employer had not legibly marked the disconnecting means for each motor and appliance as to its purpose.
Recent events (3)
  • — F (O) $3229
  • — C (S) $7813
  • — Z (S) $7813

View H.C. Blake CO., INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346204662.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.