LAKE CITY, FL —
OSHA Inspection: U.S. DEPARTMENT OF VETERAN'S AFFAIRS
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of U.S. DEPARTMENT OF VETERAN'S AFFAIRS in 619 SOUTH MARION AVE., LAKE CITY, FL 32025 (NAICS 622110). OSHA activity number 346221112.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. DEPARTMENT OF VETERAN'S AFFAIRS
- Site address
- 619 SOUTH MARION AVE.
- City
- LAKE CITY
- State
- FL
- ZIP
- 32025
- Mailing
- 619 SOUTH MARION AVE., LAKE CITY, FL 32025
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 58
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.28 B01 I
- Issued
- Jan 25, 2023
- Abate by
- Feb 21, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.28(b)(1)(i): Except as provided elsewhere in this section 29 CFR 1910.28, the employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling by one or more of the systems described in 29 CFR 1910.28(b)(1)(i): a. On or about September 14, 2022, at the boiler room, the employer exposed employees to a 10 feet fall hazard, in that, operators were required to reach hand-valves located on top of unguarded boiler tanks.
Recent events (1)
- — Z (S) $0
1910.28 B03 II
- Issued
- Jan 25, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.28(b)(3)(ii): The employer did not ensure that each employee be protected from tripping into or stepping into or through any hole that is less than 4 feet (1.2 m) above a lower level by covers or guardrail systems: a. On or about September 14, ,2022, at the northwest area behind the boiler room, the employer exposed employees to a fall hazard, in that, a temporary open hole measuring 28" deep x 34" W x 60" L did not have a protective cover or an affective guarding system. b. On or about September 14, ,2022, at the DA tank area in the 2nd floor, the employer exposed employees to a trip and fall hazard, in that, a 10 inch square floor drainage was missing a cover.
Recent events (1)
- — Z (S) $0
1910.303 G02 I
- Issued
- Jan 25, 2023
- Abate by
- Feb 21, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision: a. On or about October 18, 2022, behind the diesel pumps, the employer exposed employees to electrocution hazards, in that, an electric cable had a live exposed conductor that was not properly guarded with a cover or de-energized.
Recent events (1)
- — Z (S) $0
1910.38 C02
- Issued
- Jan 25, 2023
- Abate by
- Feb 21, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.38(c)(2):Procedures for emergency evacuation, including type of evacuation and exit route assignments were not implemented by the employer: a. On or about September 14, 2022, at the boiler room, the employer exposed employees to fire hazards, in that the employer did not have a diagram showing the designated exit routes assignments at the site.
Recent events (1)
- — Z (O) $0
1910.305 B02 I
- Issued
- Jan 25, 2023
- Abate by
- Feb 21, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: a. On or about October 18, 2022, at the front of the diesel pumps, the employer exposed employees to electric shock hazard, in that, a junction box with live conductors was missing a protective cover.
Recent events (1)
- — Z (O) $0
More inspections at U.S. Department of Veteran'S Affairs
View U.S. Department of Veteran'S Affairs's full OSHA safety record →
More inspections in this industry (NAICS 622110)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346221112.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.