Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. DEPARTMENT OF VETERAN'S AFFAIRS

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of U.S. DEPARTMENT OF VETERAN'S AFFAIRS in 619 SOUTH MARION AVE., LAKE CITY, FL 32025 (NAICS 622110). OSHA activity number 346221112.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Department of Veteran'S Affairs — free Get an email when a new federal OSHA severe-injury report for U.S. Department of Veteran'S Affairs is published. One employer, no account, unsubscribe in one click.
Site address
619 SOUTH MARION AVE.
City
LAKE CITY
State
FL
ZIP
32025
Mailing
619 SOUTH MARION AVE., LAKE CITY, FL 32025
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
58
Ownership type
D

5 citations on file for this inspection.

1910.28 B01 I

Serious Gravity 5 1 instance 4 exposed
Issued
Jan 25, 2023
Abate by
Feb 21, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.28(b)(1)(i):  Except as provided elsewhere in this section 29 CFR 1910.28, the employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling by one or more of the systems described in 29 CFR 1910.28(b)(1)(i):  a.  On or about September 14, 2022, at the boiler room, the employer exposed employees to a 10 feet fall hazard, in that, operators were required to reach hand-valves located on top of unguarded boiler tanks.
Recent events (1)
  • — Z (S) $0

1910.28 B03 II

Serious Gravity 5 2 instances 4 exposed
Issued
Jan 25, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.28(b)(3)(ii): The employer did not ensure that each employee be protected from tripping into or stepping into or through any hole that is less than 4 feet (1.2 m) above a lower level by covers or guardrail systems:  a.  On or about September 14, ,2022, at the northwest area behind the boiler room, the employer exposed employees to a fall hazard, in that, a temporary open hole measuring 28" deep x 34" W x 60" L did not have a protective cover or an affective guarding system.    b.  On or about September 14, ,2022, at the DA tank area in the 2nd floor, the employer exposed employees to a trip and fall hazard, in that, a 10 inch square floor drainage was missing a cover.
Recent events (1)
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 1 instance 4 exposed
Issued
Jan 25, 2023
Abate by
Feb 21, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:  a.  On or about October 18, 2022, behind the diesel pumps, the employer exposed employees to electrocution  hazards, in that, an electric cable had a live exposed conductor that was not properly guarded with a cover or de-energized.
Recent events (1)
  • — Z (S) $0

1910.38 C02

Other-than-serious 1 instance 4 exposed
Issued
Jan 25, 2023
Abate by
Feb 21, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.38(c)(2):Procedures for emergency evacuation, including type of evacuation and exit route assignments were not implemented by the employer:  a.  On or about September 14, 2022, at the boiler room, the employer exposed employees to fire hazards, in that the employer did not have a diagram showing the designated exit routes assignments at the site.
Recent events (1)
  • — Z (O) $0

1910.305 B02 I

Other-than-serious 1 instance 4 exposed
Issued
Jan 25, 2023
Abate by
Feb 21, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  a.  On or about October 18, 2022, at the front of the diesel pumps, the employer exposed employees to electric shock hazard, in that, a junction box with live conductors was missing a protective cover.
Recent events (1)
  • — Z (O) $0

View U.S. Department of Veteran'S Affairs's full OSHA safety record →