Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: THE NEW YORK AND PRESBYTERIAN HOSPITAL

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of THE NEW YORK AND PRESBYTERIAN HOSPITAL in 3959 BROADWAY MORGAN STANLEY CHILDREN'S HOSPITAL, NEW YORK, NY 10032 (NAICS 622110). OSHA activity number 346226541.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The NEW York and Presbyterian Hospital — free Get an email when a new federal OSHA severe-injury report for The NEW York and Presbyterian Hospital is published. One employer, no account, unsubscribe in one click.
Site address
3959 BROADWAY MORGAN STANLEY CHILDREN'S HOSPITAL
City
NEW YORK
State
NY
ZIP
10032
Mailing
3959 BROADWAY NEWYORK-PRESBYTERIAN HOSPITAL / MORGAN STANLEY CHILDREN?S HOSPITAL, NEW YORK, NY 10032
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
10767
Ownership type
A

3 citations on file for this inspection.

1926.403 H

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Mar 10, 2023
Abate by
Mar 17, 2023
Penalty
Initial $14,063 · Current $0 Reduced
29 CFR  1926.403(h): Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident:  a) Patient Room CHT 1003   On or about 9/14/22 and 9/15/22, electricians were working to remove energized electrical cables of 277 volts. The disconnecting means for the circuit was not legibly marked to indicate its purpose, nor located and arranged so that the purpose was evident.
Recent events (3)
  • — F (S) $0
  • — C (S) $14063
  • — Z (S) $14063

1926.403 I02 I

Other-than-serious Gravity 5 1 instance 4 exposed
Issued
Mar 10, 2023
Abate by
Mar 17, 2023
Penalty
Initial $10,046 · Current $10,046
29 CFR  1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph:  a) Patient Room CHT 1003  On or about 9/14/22 and 9/15/22, live electrical wiring of 277 volts were not guarded against accidental contact by cabinets or other forms of enclosures.
Recent events (3)
  • — F (O) $10046
  • — C (S) $10046
  • — Z (S) $10046

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Mar 10, 2023
Abate by
Mar 17, 2023
Penalty
Initial $14,063 · Current $14,063
29 CFR  1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:   a) Patient Room CHT 1003  On or about 9/14/22 and 9/15/22, electricians were working on live electrical wiring of 277 volts and were exposed to electrical shock.