NEW LONDON, CT —
OSHA Inspection: U.S. COAST GUARD ACADEMY
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of U.S. COAST GUARD ACADEMY in 15 MOHEGAN AVENUE, NEW LONDON, CT 06372 (NAICS 611310). OSHA activity number 346239080.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. COAST GUARD ACADEMY
- Site address
- 15 MOHEGAN AVENUE
- City
- NEW LONDON
- State
- CT
- ZIP
- 06372
- Mailing
- 15 MOHEGAN AVENUE, NEW LONDON, CT 06372
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 611310
- Employees
- 300
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.23 D02
- Issued
- Nov 17, 2022
- Abate by
- Jan 6, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(d)(2):29 CFR 1910.23(d)(2): The employer did not ensure that the minimum perpendicular distance from the centerline of the steps or rungs, or grab bars, or both, to the nearest permanent object in back of the ladder is 7 inches (18 cm), except for elevator pit ladders, which have a minimum perpendicular distance of 4.5 inches (11 cm): McAllister Hall Tunnel Entrance: As required by the referenced standard and 29 CFR 1960.8(b): On, or about, September 19, 2022, the three rung, fixed ladder that provided access to/egress from the tunnel had obstructions behind the ladder due to the installation of pipes.
Recent events (1)
- — Z (S) $0
1910.23 D04
- Issued
- Nov 17, 2022
- Abate by
- Jan 6, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(d)(4): The employer did not ensure that the side rails of through or sidestep ladders extend at least 42 inches (1.1 m) above the top of the access level or landing platform served by the ladder: McAllister Hall Tunnel Entrance: As required by the referenced standard and 29 CFR 1960.8(b): On, or about, September 19, 2022, the three rung, fixed ladder that provided access to/egress from the tunnel was not provided with ladder extensions, a grab bar or other suitable hand-hold for employees to use for stability while using the ladder.
Recent events (1)
- — Z (S) $0
1910.146 C01
- Issued
- Nov 17, 2022
- Abate by
- Jan 6, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.146(c)(1): The employer did not evaluate the workplace to determine if any spaces were permit-required confined spaces: Sail Loft Unfinished Basement: As required by the referenced standard and 29 CFR 1960.8(b): On, or about, September 19, 2022, the unfinished portion on the basement level was contained plumbing and electrical systems and was used for storage. The space had limited access/egress, contained non-contained asbestos fibers, airborne mold particles/spores, was cluttered and contained tripping hazards, was not provided with lighting and did not appear to meet Life Safety Codes for egress. The space had not been evaluated under the the Confined Space Identification and Entry Program. Abatement Note: In addition to evaluating the space for confined space hazards, the atmospheric hazards created by the presence of asbestos and mold need to be identified and quantified to determine the proper level of respiratory protection to be worn by entrants in the future under a Respiratory Protection Program that includes medical evaluations, fit-testing and training.
Recent events (1)
- — Z (S) $0
1910.303 H02 III A
- Issued
- Nov 17, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(h)(2)(iii)(A): Conductors and equipment used on circuits exceeding 600 volts, nominal: The installations shall be made with metal-enclosed equipment or shall be enclosed in a vault or in an area to which access is controlled by a lock; McAllister Hall Tunnel Entrance: As required by the referenced standard and 29 CFR 1960.8(b): On, or about, September 19, 2022, the door providing access to the tunnel entrance was not kept locked. The room contained 13,200 volt conductors that although insulated, were not protected from accidental contact by an enclosure, barrier, or fence.
Recent events (1)
- — Z (S) $0
1910.335 B01
- Issued
- Nov 17, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(b)(1): Safety signs, safety symbols, or accident prevention tags were not used where necessary to warn employees about electrical hazards which may endanger them: McAllister Hall Tunnel Entrance: As required by the referenced standard and 290 CFR 1960.8(b): On, or about, September 19, 2022, the door providing access to the tunnel entrance was not provided with signage to inform employees that live electrical equipment was located inside of the room. The room housed 13,200 volt conductors that although insulated, were not protected from accidental contact by an enclosure, barrier or fence.
Recent events (1)
- — Z (S) $0
More inspections at U.S. Coast Guard Academy
View U.S. Coast Guard Academy's full OSHA safety record →
More inspections in this industry (NAICS 611310)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346239080.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.