DALLAS, TX —
OSHA Inspection: CENVEO, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of CENVEO, INC. in 14001 INWOOD ROAD, DALLAS, TX 75244 (NAICS 322230). OSHA activity number 346266315.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CENVEO, INC.
- Site address
- 14001 INWOOD ROAD
- City
- DALLAS
- State
- TX
- ZIP
- 75244
- Mailing
- 14001 INWOOD ROAD, DALLAS, TX 75244
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 322230
- Employees
- 214
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.178 L01 I
- Issued
- Feb 13, 2023
- Abate by
- Feb 24, 2023
- Penalty
- Initial $15,625 · Current $15,625
General-duty citation text
29 CFR 1910.178(l)(1)(i): The employer did not ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l): a) This violation occurred on or about October 6, 2022 and at times prior thereto; when employees were operating the forklift without having formal instruction and practical training.
Recent events (2)
- — C (S) $15625
- — Z (S) $15625
1910.212 A01
- Issued
- Feb 13, 2023
- Abate by
- Feb 24, 2023
- Penalty
- Initial $15,625 · Current $15,625
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks. a) This violation occurred on or about October 6, 2022, and at times prior thereto; in production plant, where employees were exposed to being caught-in or struck-by the unguarded pinch points created by rotating shafts: a. Envelope machine, FL Smithe, SW-5013, at the refeed/aligner section. b. Envelope machine, FL Smithe, SW-5021, at the Refeed/Aligner section. c. Envelope machine, FL Smithe, SW-5022, at the Refeed/Aligner section.
Recent events (2)
- — C (S) $15625
- — Z (S) $15625
1910.303 B02
- Issued
- Feb 13, 2023
- Abate by
- Feb 24, 2023
- Penalty
- Initial $11,162 · Current $11,162
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: The employer did not ensure electrical equipment is used and installed in accordance with the listing or labeling instructions. This violation occurred on or about October 6, 2022, and at times prior thereto; in the production plant, envelope machines areas: a) Power tap/power strip was being used to provide power to the light at envelope machine FL Smithe, SW-5013. b) Power tap/power strip was being used to provide power to the light at envelope machine FL Smithe, SW-5021. c) Power tap/power strip was being used to provide power to the light at envelope machine FL Smithe, SW-5022.
Recent events (2)
- — C (S) $11162
- — Z (S) $11162
1910.303 F02
- Issued
- Feb 13, 2023
- Abate by
- Feb 24, 2023
- Penalty
- Initial $11,162 · Current $11,162
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) This violation occurred on or about October 6, 2022, and at times prior thereto; In production plant, where circuit breaker panels were not marked to indicate the purpose of individual breakers. a. Panel A, in folding area. b. Panel 277B, in folding area. c. Panel 277-3, in shipping area (upstairs).
Recent events (2)
- — C (S) $11162
- — Z (S) $11162
1910.303 G01
- Issued
- Feb 13, 2023
- Abate by
- Feb 24, 2023
- Penalty
- Initial $11,162 · Current $11,162
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. a) On or about October 6, 2022, and at times prior thereto; In shipping department, electrical disconnect and transformer were blocked by large commercial printer, boxes and materials.
Recent events (2)
- — C (S) $11162
- — Z (S) $11162
More inspections at Cenveo, INC.
View Cenveo, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 322230)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346266315.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.