Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DUSIT BEACH RESORT GUAM L.P.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DUSIT BEACH RESORT GUAM L.P. in 1227 PALE SAN VITORES ROAD, TAMUNING, GU 96913 (NAICS 721110). OSHA activity number 346279706.

Watch Dusit Beach Resort Guam L.P. — free Get an email when a new federal OSHA severe-injury report for Dusit Beach Resort Guam L.P. is published. One employer, no account, unsubscribe in one click.
Site address
1227 PALE SAN VITORES ROAD
City
TAMUNING
State
GU
ZIP
96913
Mailing
1227 PALE SAN VITORES ROAD, TAMUNING, GU 96913
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
190
Ownership type
A

4 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 1 1 instance 18 exposed
Issued
Penalty
Initial $4754.00 · Current $3328.00 Reduced
29 CFR  1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  Engineering Department, Chemical Storage Area, above the HAZMAT locker: A junction box with exposed live wires was partially uncovered.  Employees were exposed to electrical hazards.
Recent events (2)
  • — I (S) $3327.8
  • — Z (S) $4754

1910.37 B06

Other-than-serious 1 instance 18 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  Engineering Area in Basement, above exit to garage: The emergency exit was labeled with a non-functioning Exit sign. Employees were exposed to egress impediments.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 B02

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Front desk area, by cash machine: Two relocatable power taps (RPTs) and an extension cord were connected in-series (daisy chained) that provided power to the cash machine. Employees were exposed to fire and electrical hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01

Other-than-serious 1 instance 5 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  Hotel Front Desk Area: Electrical panel 2PC and electrical panel 2LP were blocked by express check out card holders and other storage. Access was restricted in the event of an emergency.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View DUSIT BEACH RESORT GUAM L.P.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346279706.