TAMUNING, GU —
OSHA Inspection: PREMIER HOTELS & RESORTS GUAM, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of PREMIER HOTELS & RESORTS GUAM, INC. in 470 FARENHOLT AVE, TAMUNING, GU 96913 (NAICS 721110). OSHA activity number 346279722.
Where did this inspection happen?
- Establishment
- PREMIER HOTELS & RESORTS GUAM, INC.
- Site address
- 470 FARENHOLT AVE
- City
- TAMUNING
- State
- GU
- ZIP
- 96913
- Mailing
- 470 FARENHOLT AVE, TAMUNING, GU 96913
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 193
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.147 C04 I
- Issued
- Abate by
- Penalty
- Initial $5594.00 · Current $3916.00 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: A) In Guest Room 806: There was no established lockout tagout program to instruct on how to replace the blower of an air conditioning unit. Employees were exposed to laceration and electrical hazards. B) Guest Room: There was was no established lockout tagout program to instruct on how to perform replacement of a fan coil unit to perform maintenance of an air conditioning unit. Employees were exposed to laceration and electrical hazards.
Recent events (2)
- — I (S) $3915.8
- — Z (S) $5594
1910.213 C01
- Issued
- Penalty
- Initial $7925.00 · Current $5548.00 Reduced
General-duty citation text
29 CFR 1910.213(c)(1): Circular handfed ripsaw(s) were not guarded by an automatically adjusting hood which completely enclosed that portion of the saw above the table and above the material being cut: Plant Room: The blade above the table portion of a homemade table saw used to cut wood was not guarded. Employees were exposed to laceration and amputation hazards.
Recent events (2)
- — I (S) $5547.5
- — Z (S) $7925
1910.37 A04
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: Service Elevator Lobby: The emergency light did not work when tested. Employees were exposed to fire and evacuation hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 B02
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Maintenance Area Office, under the bulletin board: A relocatable power tap secured to the wall with screws, was used to provide power to two Ridgid battery chargers. Employees were exposed to fire and electrical hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: A) Maintenance Area Office, next to Siemens Exhaust Fan shut-off and Right-To-Know Station: Access to three electrical panels was blocked by storage. Employees were exposed to electrical hazards. B) Plant Room, Maintenance Work Area, by chop saw: Access to electrical panel was blocked by storage. Employees were exposed to electrical hazards. C) Plant Room, Back, switches CHWP-1 and CHWP-4: Access to emergency shut-offs was blocked by storage. Employees were exposed to electrical hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at PREMIER HOTELS & RESORTS GUAM, INC.
TAMUNING, GU—2022-10-12 00:00:00
PREMIER HOTELS & RESORTS GUAM, INC.
View PREMIER HOTELS & RESORTS GUAM, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 721110)
SAN RAFAEL, CA—2026-07-17 00:00:00
EQUINOX UGI SR INVESTMENTS, LLC
PALM SPRINGS, CA—2026-07-16 00:00:00
LA SERENA VILLAS
BOISE, ID—2026-07-16 00:00:00
RAYMOND MANAGEMENT COMPANY
ORLANDO, FL—2026-07-16 00:00:00
EVERMORE ORLANDO RESORT
LAS VEGAS, NV—2026-07-15 00:00:00
THE MARCUS CORPORATION ETAL
More inspections in GU
BARRIGADA, GU—2026-01-22 00:00:00
DURI CORPORATION
TAMUNING, GU—2026-01-21 00:00:00
DLR CORPORATION
BARRIGADA, GU—2026-01-21 00:00:00
DURI CORPORATION
TAMUNING, GU—2026-01-20 00:00:00
MG CONSTRUCTION COMPANY
BARRIGADA, GU—2026-01-20 00:00:00
PFM -VERTEX-LMS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346279722.