OSHA Inspection: AHLSTROM MUNKSJO NA SPECIALTY SOLUTIONS LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of AHLSTROM MUNKSJO NA SPECIALTY SOLUTIONS LLC in 600 THILMANY ROAD, KAUKAUNA, WI 54130 (NAICS 322121). OSHA activity number 346295041.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ahlstrom Munksjo NA Specialty Solutions LLC — free Get an email when a new federal OSHA severe-injury report for Ahlstrom Munksjo NA Specialty Solutions LLC is published. One employer, no account, unsubscribe in one click.
Site address
600 THILMANY ROAD
City
KAUKAUNA
State
WI
ZIP
54130
Mailing
600 THILMANY ROAD, KAUKAUNA, WI 54130
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322121
Employees
550
Ownership type
A

6 citations on file for this inspection.

1910.178 A04

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 2, 2023
Abate by
Apr 17, 2023
Penalty
Initial $9,822 · Current $5,893 Reduced
29 CFR  1910.178(a)(4):  Modifications and additions which affect capacity and safe operation shall not be performed by the customer or user without manufacturers prior written approval. Capacity, operation, and maintenance instruction plates, tags, or decals shall be changed accordingly.  During the weekend of September 17, 2022 and thereafter, at an establishment located at 600 Thilmany Road, in Kaukauna, Wisconsin in the Material Prep Department; a Hyster Lift Truck Model: E60XN-33, S/N: A268N03993H with an unapproved pan attachment was used to move rolls in and out of the splitter and into a bin.  The employer did not get the forklift manufacturers prior written approval and did not update the nameplate as required.
Recent events (2)
  • — I (S) $5893.2
  • — Z (S) $9822

1910.332 B02

Serious Gravity 5 2 instances 2 exposed
Issued
Feb 2, 2023
Abate by
Mar 10, 2023
Penalty
Initial $12,278 · Current $7,367 Reduced
29 CFR  1910.332(b)(2):  Additional requirements for unqualified persons. Employees who are covered by paragraph (a) of this section but who are not qualified persons shall also be trained in and familiar with any electrically related safety practices not specifically addressed by 1910.331 through 1910.335 but which are necessary for their safety.  On or about the weekend of September 17, 2022, at an establishment located at 600 Thilmany Road, in Kaukauna, Wisconsin, in the Material Prep Department, unqualified employees performing activities such as but not limited to troubleshooting activities on a Richmond Engineering, Series 7200 C Roll Splitter  were not trained in the safe electrical practices exposing the employees to electrical shock hazards.
Recent events (2)
  • — I (S) $7366.8
  • — Z (S) $12278

1910.333 A02

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 2, 2023
Abate by
Mar 10, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.333(a)(2): "Energized parts." If the exposed live parts are not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices shall be used to protect employees who may be exposed to the electrical hazards involved. Such work practices shall protect employees against contact with energized circuit parts directly with any part of their body or indirectly through some other conductive object. The work practices that are used shall be suitable for the conditions under which the work is to be performed and for the voltage level of the exposed electric conductors or circuit parts. Specific work practice requirements are detailed in paragraph (c) of this section.   On or about the weekend of September 17, 2022, at an establishment located at 600 Thilmany Road, in Kaukauna, Wisconsin, in the Material Prep Department, unqualified employees troubleshooting the Richmond Engineering, Series 7200 C Roll Splitter were exposed to electrical hazards.  The employer did not ensure electrical safe work practices were employed.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 C02

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 2, 2023
Abate by
Mar 10, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.333(c)(2): "Work on energized equipment." Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.  On or about the weekend of September 17, 2022, at an establishment located at 600 Thilmany Road, in Kaukauna, Wisconsin, in the Material Prep Department, unqualified employees exposed to live conductors while troubleshooting a Richmond Engineering, Series 7200 C Roll Splitter were unfamiliar with the proper use of personal protective equipment, safety techniques, and insulating materials and tools while being exposed to electrical shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A02 II

Serious Gravity 5 1 instance 3 exposed
Issued
Feb 2, 2023
Abate by
Mar 3, 2023
Penalty
Initial $12,278 · Current $7,367 Reduced
29 CFR  1910.334(a)(2)(ii): If there is a defect or evidence of damage that might expose an employee to injury, the defective or damaged item shall be removed from service, and no employee may use it until repairs and tests necessary to render the equipment safe have been made.   On or about October 20, 2022 at an establishment located at 600 Thilmany Road, in Kaukauna, Wisconsin in the 12 Stock Prep Area;  the Revolution KCHG29 forklift battery charger was not removed from damage until repairs were made.  Electrical tape was wrapped around in several locations covering up the damaged electrical jacket exposing employees to electrical shock hazards.
Recent events (2)
  • — I (S) $7366.8
  • — Z (S) $12278

1910.305 B01 II

Other-than-serious 1 instance 2 exposed
Issued
Feb 2, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.305(b)(1)(ii):  Unused openings in cabinets, boxes, and fittings shall be effectively closed.  During the weekend of September 17, 2022 and thereafter, at an establishment located at 600 Thilmany Road, in Kaukauna, Wisconsin in the Material Prep Department; the Richmond Engineering, Series 7200 C Roll Splitter had a pull box that was not effectively closed with energized wires routing to the operator's control box splitter exposing employees to electrical shock hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Ahlstrom Munksjo NA Specialty Solutions LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346295041.