NORMAL, IL —
OSHA Inspection: RIVIAN AUTOMOTIVE, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of RIVIAN AUTOMOTIVE, LLC in 100 RIVIAN MOTORWAY, NORMAL, IL 61761 (NAICS 336111). OSHA activity number 346297310.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RIVIAN AUTOMOTIVE, LLC
- Site address
- 100 RIVIAN MOTORWAY
- City
- NORMAL
- State
- IL
- ZIP
- 61761
- Mailing
- 100 RIVIAN MOTORWAY ATTN: MIKE IRWIN, NORMAL, IL 61761
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336111
- Employees
- 8000
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.22 D01
- Issued
- Feb 10, 2023
- Abate by
- Mar 14, 2023
- Penalty
- Initial $10,436 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.22(d)(1): The employer did not ensure that walking-working surfaces are inspected, regularly and as necessary, and maintained in a safe condition On October 20, 2022, the employer failed to fully inspect a walking working surface in the Weld Destruct Tent to ensure that it was maintained free and clean of unused tools, extension cords, and water intrusion.
Recent events (2)
- — I (O) $2500
- — Z (S) $10436
1910.22 A02
- Issued
- Feb 10, 2023
- Abate by
- Mar 14, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(2): The employer had not ensured that the floor of each workroom was maintained in a clean and, to the extent feasible, in a dry condition: On or about October 20, 2022, employees working in the Weld Destruct Tent were exposed to slips and falls because the employer had not ensured that the work area was maintained in a dry condition during periods of heavy rain.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 I A
- Issued
- Feb 10, 2023
- Abate by
- Mar 14, 2023
- Penalty
- Initial $8,349 · Current $7,500 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: On or about October 20, 2022, employees working in the Weld Destruct Tent were exposed to electric shock hazards and the employer had not ensured electric panels, disconnects, and circuit breakers were unobstructed.
Recent events (2)
- — I (O) $7500
- — Z (S) $8349
1910.303 B01
- Issued
- Feb 10, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: On October 20, 2022, the Company failed to ensure that yellow extension cords that had a missing grounding pin or a damaged jacket were removed from service, rather than plugged into GFCI outlets.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 B07
- Issued
- Feb 10, 2023
- Abate by
- Mar 14, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7): Electrical equipment was not installed in a neat and workmanlike manner: On or about October 20, 2022, employees working in the Weld Destruct Tent were exposed to electric shock hazards because the employer had not ensured the conduit and other electrical components branching from the portable electric panels were installed in a neat and workmanlike manner.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Rivian Automotive, LLC