FORT WORTH, TX —
OSHA Inspection: MOLSON COORS BEVERAGE COMPANY USA LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MOLSON COORS BEVERAGE COMPANY USA LLC in 7001 SOUTH FREEWAY, FORT WORTH, TX 76134 (NAICS 312120). OSHA activity number 346333776.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MOLSON COORS BEVERAGE COMPANY USA LLC
- Site address
- 7001 SOUTH FREEWAY
- City
- FORT WORTH
- State
- TX
- ZIP
- 76134
- Mailing
- 7001 SOUTH FREEWAY, FORT WORTH, TX 76134
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 312120
- Employees
- 509
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.119 E03 V
- Issued
- Apr 27, 2023
- Abate by
- Aug 1, 2023
- Penalty
- Initial $6,696 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(e)(3)(v): The process safety hazard analysis did not address facility siting. On or about 11/08/2022, at the Molson Coors facility located in Fort Worth Texas, the employer did not address a facility siting in process hazard analysis (PHA). This condition potentially exposed employees to fire and explosion.
Recent events (2)
- — I (S) $0
- — Z (S) $6696
1910.119 J02
- Issued
- Apr 27, 2023
- Abate by
- Jun 16, 2023
- Penalty
- Initial $6,696 · Current $6,696
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going integrity of process equipment. On or about 11/08/2023 at the Molson Coors facility located in Fort Worth Texas, employees were exposed to anhydrous ammonia release hazards when the employer did not ensure that written procedures for testing of process equipment were established and implemented including but not limited to: a. Written a high discharge temperature cutout procedure for Sullair compressor #3, No. 200C31 (P&ID 402-10-7002). b. Written a low oil pressure cutout procedure for Sullair compressor #7, No. 200C71 (P&ID 402-10-7003). c. Written a low suction pressure and high discharge pressure cutout procedure for Sullair compressor #10 No. 7592A-2-C1 (P&ID 402-10-7003.
Recent events (2)
- — I (O) $6696
- — Z (S) $6696
1910.119 L01
- Issued
- Apr 27, 2023
- Penalty
- Initial $6,696 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119 (l)(1): The employer did not establish and implement written procedures to manage changes (except for "replacements in kind") to process chemicals, technology, equipment, and procedures; and changes to facilities that affect a covered process. On or about 02/04/2023, at the Molson Coors facility located in Fort Worth Texas, the employer did not establish and implement written procedures to manage changes such as to replace the discharge isolation valve (G067) on #1 Sullair compressor and install a new pumpout connection with a pumpout valve (P070) between the isolation valve and a check valve.
Recent events (2)
- — I (S) $0
- — Z (S) $6696
1910.119 J04 IV
- Issued
- Apr 27, 2023
- Abate by
- Aug 1, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(j)(4)(iv): The employer did not document each inspection and test that has been performed on process equipment. The documentation did not identify the date of the inspection or test, the name of the person who performed the inspection or test, the serial number or other identifier of the equipment on which the inspection or test was performed, a description of the inspection or test performed, and the results of the inspection or test. On or about 11/8/2022, at the Molson Coors facility located in Fort Worth Texas, the employer did not document each inspection and test that has been performed on process equipment including but not limited to: a. High discharge temperature cut out for the compressor Sullair #3 No. 200C31 (P&ID 402-10-7002). b. Low oil pressure cut out for the compressor Sullair #7 No. 200C71 (P&ID 402-10-7003) c. Low suction pressure and high discharge pressure cut outs for the compressor Sullair #10 No. 7592A-2-C1 (P&ID 402-10-7003). d. Pressure transmitter PIT-01 for PV-1 Accumulator (P&ID 402-10-4518). e. Level alarm, 401-LSH-001, for Ammonia Suction Trap No.1 (No. 1209, P&ID 402-10-7007). f. The emergency stop button for the king valve located in the control room. g. The emergency stop button for the king valve located at West entrance door of the powerhouse (or engine room). h. The emergency stop button for ammonia compressors located in the control room. i. The emergency stop button for ammonia compressor located at West entrance door of the powerhouse (or engine room). j. The emergency ventilation control switch or "EF Emergency Override" button located at West entrance door of the powerhouse (or engine room). k. Ammonia detector, XT001 (IR-F9-0/2%-N1) l. Ammonia detector, XT002 (EC-F9-0/1000-N1) m. Ammonia detector, XT003 (EC-F0-0/100-N1) n. Ammonia detector, XT007 (IR-F9-0/2%-N1) o. Ammonia detector, XT008 (EC-F9-0/1000-N1) p. Ammonia detector, XT009 (EC-F0-0/100-N1)
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Molson Coors Beverage Company USA LLC
View Molson Coors Beverage Company USA LLC's full OSHA safety record →
More inspections in this industry (NAICS 312120)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346333776.