Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: UNITED STATES POSTAL SERVICE

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of UNITED STATES POSTAL SERVICE in 401 OGLETOWN ROAD, NEWARK, DE 19711 (NAICS 491110). OSHA activity number 346359318.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch United States Postal Service — free Get an email when a new federal OSHA severe-injury report for United States Postal Service is published. One employer, no account, unsubscribe in one click.
Site address
401 OGLETOWN ROAD
City
NEWARK
State
DE
ZIP
19711
Mailing
401 OGLETOWN ROAD, NEWARK, DE 19711
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
491110
Employees
130
Ownership type
A

10 citations on file for this inspection.

1910.37 A04

Serious Gravity 5 1 instance 4 exposed
Issued
May 26, 2023
Abate by
Jun 23, 2023
Penalty
Initial $9,822 · Current $4,911 Reduced
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times:     a) 401 Ogletown Road, Newark DE 19711 (Postmaster Office Hallway): On or about November 29, 2022, CSHO observed emergency exit hazards related to emergency evacuation of the building including but not limited to the exit sign in the Postmaster office hallway leading to the exit access was not illuminated to ensure visibility in the event of an emergency evacuation.
Recent events (3)
  • — F (S) $4911
  • — C (S) $9822
  • — Z (S) $9822

1910.37 B02

Deleted Serious Gravity 5 1 instance 9 exposed
Issued
May 26, 2023
Abate by
Jun 23, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2):Each exit was not clearly visible and marked by a sign reading "Exit":    a) 401 Ogletown Road, Newark DE 19711 (Exit door labeled #3): On or about November 29, 2022, CSHO observed an available exit door, number 3, that was indicated as an exit on the facility map that did not have an exit sign posted indicating it as an exit.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.303 B07 IV

Serious Gravity 5 3 instances 1 exposed
Issued
May 26, 2023
Abate by
Jun 23, 2023
Penalty
Initial $9,822 · Current $4,911 Reduced
29 CFR 1910.303(b)(7)(iv):Electrical equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:    a) 401 Ogletown Road, Newark DE 19711 (LTG. Panel LP-3): On or about November 29, 2022, CSHO observed a hasp and machine screws drilled into the electrical equipment which were not maintained to manufacturer specifications.      b) 401 Ogletown Road, Newark DE 19711 (Column 5): On or about November 29, 2022, CSHO observed a hasp and machine screws drilled into the electrical equipment which were not maintained to manufacturer specifications.    c) 401 Ogletown Road, Newark DE 19711 (Column 3): On or about November 29, 2022, CSHO observed a hasp and machine screws drilled into the electrical equipment which were not maintained to manufacturer specifications.
Recent events (3)
  • — F (S) $4911
  • — C (S) $9822
  • — Z (S) $9822

1910.303 B02

Deleted Serious Gravity 5 2 instances 1 exposed
Issued
May 26, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   a) 401 Ogletown Road, Newark DE 19711 (Column C5): On or about November 29, 2022, CSHO observed access to the electrical equipment were not maintained to permit ready and safe access in that the space around the 240V panel was limited due the bollards installed measured 17 inches from the front of panel and the sides measured 20 inches from the side of panel.      b) 401 Ogletown Road, Newark DE 19711 (Column C3): On or about November 29, 2022, CSHO observed access to the electrical equipment was not maintained to permit ready and safe access in that the space around the 240V panel. CSHO through visual observations determined that the guard rail system erected around column C3 was within 30 inches of the panel.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 5 2 instances 1 exposed
Issued
May 26, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:      a) 401 Ogletown Road, Newark DE 19711 (Column C3): On or about November 29, 2022, CSHO observed access to the electrical equipment was not maintained to permit ready and safe operation in that the space around the 240V equipment was used for storage to include but not limited to cardboard boxes, loss papers, and cases of copy paper.     b) 401 Ogletown Road, Newark DE 19711 (Column C5): On or about November 29, 2022, CSHO observed access to the electrical equipment was not maintained to permit ready and safe operation in that the space around the 240V equipment was used for storage to include but not limited to mail carts with trays of letters and bins with heavy parcels.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.1200 H

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
May 26, 2023
Abate by
Jun 23, 2023
Penalty
Initial $14,733 · Current $0 Reduced
29 CFR 1910.1200(h): Employees were not provided effective information and training as specified in 29 CFR 1910.1200(h)(1) and -2 on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard was introduced.      a) 401 Ogletown Road, Newark DE 19711 (Maintenance Area): On or about November 29, 2022, and at times prior thereto, employees who use hazardous chemicals such as, but not limited to, Stampede heavy-duty floor finish (55-gallon drum) were not provided training in the hazard communication standard as required when a new hazard was introduced.
Recent events (3)
  • — F (S) $0
  • — C (S) $14733
  • — Z (S) $14733

1910.1200 G08

Serious Gravity 5 1 instance 1 exposed
Issued
May 26, 2023
Penalty
Initial $0 · Current $4,911
29 CFR 1910.1200(g)(8): The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical    a) 401 Ogletown Road, Newark DE 19711 (Maintenance Area): On or about November 29, 2022, and at times prior thereto, employees who use hazardous chemicals such as, but not limited to, Stampede heavy-duty floor finish (55-gallon drum) were not provided the safety data sheet (SDS) for the chemical placed in their work area.
Recent events (3)
  • — F (S) $4911
  • — C (S) $0
  • — Z (S) $0

1910.1200 H02 III

Serious Gravity 5 1 instance 1 exposed
Issued
May 26, 2023
Abate by
Jun 23, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(h)(2)(iii):The employer did not provide information to the employees as to the location and availability of the written hazard communication program, and material safety data sheets required by 29 CFR 1910.1200:   a) 401 Ogletown Road, Newark DE 19711 (Maintenance Area): On or about November 29, 2022, and at times prior thereto, employees who use or exposed to  hazardous chemicals such as, but not limited to, Stampede heavy-duty floor finish (55-gallon drum) were not provided training in the hazard communication standard as required when a new hazard was introduced.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.36 D01

Repeat Gravity 5 2 instances 10 exposed
Issued
May 26, 2023
Abate by
Jun 23, 2023
Penalty
Initial $61,391 · Current $20,000 Reduced
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:  a) 401 Ogletown Road, Newark DE 19711: On or about November 29, 2022, CSHO observed key operated dead bolt locks attached to exit doors. These locks expose employees to fire hazards.   b) 401 Ogletown Road, Newark DE 19711: On or about November 29, 2022, CSHO observed a magnetic lock system attached to exit doors. The doors are locked by a magnet that requires special knowledge to exit.  This system exposes employees to delayed egress and fire hazards.  The (U.S. Postal Service) was previously cited for a violation of this occupational safety and health standard or its equivalent standard (29 CFR 1910.36(d)(1)), which was contained in OSHA inspection number_1328027_ citation number_1 , item number_1_ and was affirmed as a final order on (5-7-2019), with respect to a workplace located at_560 Huyler Street South Hackensack New Jersey, 07606_.
Recent events (3)
  • — F (R) $20000
  • — C (R) $61391
  • — Z (R) $61391

1910.37 A03

Repeat Gravity 5 2 instances 10 exposed
Issued
May 26, 2023
Penalty
Initial $122,782 · Current $50,000 Reduced
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:   a) 401 Ogletown Road, Newark DE 19711(Re-shipper Area): On or about November 29, 2022, and at times prior thereto, impediments to the exit routes, created by placed packages, mobile bins, and palletized packages that blocked the exit paths, were not minimized exposing employees to trip hazards and a delayed egress in the event of an emergency.   a) 401 Ogletown Road, Newark DE 19711(Door #4/Cage): On or about November 29, 2022, and at times prior thereto, impediments to the exit routes, created by placed packages, mobile bins, and palletized packages that blocked the exit paths, were not minimized exposing employees to trip hazards and a delayed egress in the event of an emergency.    The U. S. Postal Service  was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(a)(3), which was contained in OSHA inspection number 1442354, citation number 1, item number 1 and was affirmed as a final order on (8-9-2021), with respect to a workplace located at 3649 Evergreen Parkway EVERGREEN, CO 80439.  The U. S. Postal Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(a)(3), which was contained in OSHA inspection number 1297911, citation number 1, item number 1b, and was affirmed as a final order on May 11, 2018, with respect to a workplace located at 751 Palisades Avenue in Teaneck, New Jersey.  The U. S. Postal Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(a)(3), which was contained in OSHA inspection number 1295472, citation number 1, item number 1a, and was affirmed as a final order on May 11, 2018, with respect to a workplace located at 4600 Aldine Bender Rd. in North Houston, Texas.
Recent events (3)
  • — F (R) $50000
  • — C (R) $122782
  • — Z (R) $122782

View United States Postal Service's full OSHA safety record →