Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NAVSUP FLEET LOGISTICS CENTER SAN DIEGO

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NAVSUP FLEET LOGISTICS CENTER SAN DIEGO in 3985 CUMMINGS ROAD BLDG 116, SAN DIEGO, CA 92136 (NAICS 493190). OSHA activity number 346362247.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Navsup Fleet Logistics Center SAN Diego — free Get an email when a new federal OSHA severe-injury report for Navsup Fleet Logistics Center SAN Diego is published. One employer, no account, unsubscribe in one click.
Site address
3985 CUMMINGS ROAD BLDG 116
City
SAN DIEGO
State
CA
ZIP
92136
Mailing
3985 CUMMINGS ROAD, SAN DIEGO, CA 92136
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493190
Employees
275
Ownership type
D

5 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 4 instances 23 exposed
Issued
Dec 20, 2022
Abate by
Jan 3, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On and/or before November 28, 2022, Multiple appliances such as microwaves, coffee makers and space heaters were plugged into relocatable power taps and/or "daisy chained" in which were not used according to listing and labeling instructions. This condition potentially exposed employee(s) to electrical shock and/or fire hazards.  In the following locations: a) First floor, Security Managers Office: Daisy chained power strips with space heater connected to power strip. b) Third floor room 340 back wall: Coffee maker plus microwave were connected to one extension cord.  c) 2nd floor 430 Fleet support Cubical Number 2NW112: Two extension cords daisy chained. d) First floor main entrance  secretary's desk: Space heater was connected to extension cord.
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 5 1 instance 32 exposed
Issued
Dec 20, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage  1st Floor Bulk Area: On and/or before November 28, 2022 the employer did not ensure at least 3 feet in front of electrical panels and switch boxes was clear. The circuit breaker panel was blocked by a cart in which the circuit breaker panel had powered offices, lights, women, and men's restrooms. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. Employee(s) were potentially exposed to electrical shock and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 2 instances 32 exposed
Issued
Dec 20, 2022
Abate by
Jan 3, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose  On and/or before November 28, 2022 the electrical transfer box cover was open and not secured to the box housing and/or missing a knock out cover showing exposed wiring. Employees continuously work in these areas loading and/or offloading shelves or administrative work. This condition potentially exposed employee(s) to electrical shock, and or fire hazard(s).  Located in: a) First Floor physical distribution cage, center of cage next to the wall.  b) Second floor next to cubical 2NE033.
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 20, 2022
Abate by
Jan 3, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws.   First floor second cubical from south eastside warehouse garage door (Open purchase area): On and/or before November 28, 2022, a relocatable power strip had damage to the outer jacket next to the male end of the cord. This condition potentially exposed employee(s) to electrical shock, and or fire hazard(s).
Recent events (1)
  • — Z (S) $0

1910.157 E03

Other-than-serious 2 instances 32 exposed
Issued
Dec 20, 2022
Abate by
Jan 10, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check  1st floor warehouse: On or before November 28, 2022 fire extinguisher(s) mounted/staged were not up to date with their annual maintenance check. Tag(s) reads 2017.  In the following Locations: a) Located on the first floor of Bldg 116, next to the southwest side double doors and cousins LP 1100 machine. b) Located on the first floor of Bldg 116, in between the emergency exit and the northeast side warehouse garage door.
Recent events (1)
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346362247.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.