Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: UNITED ELECTRIC COOPERATIVE

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of UNITED ELECTRIC COOPERATIVE in 27606 HIGHWAY F, MARYVILLE, MO 64468 (NAICS 237130). OSHA activity number 346386170.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch United Electric Cooperative — free Get an email when a new federal OSHA severe-injury report for United Electric Cooperative is published. One employer, no account, unsubscribe in one click.
Site address
27606 HIGHWAY F
City
MARYVILLE
State
MO
ZIP
64468
Mailing
401 N. U.S. BUSINESS 71, SAVANNAH, MO 64485
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237130
Employees
120
Ownership type
A

3 citations on file for this inspection.

1926.960 B02

Serious Gravity 10 1 instance 2 exposed
Issued
May 24, 2023
Abate by
Jun 29, 2023
Penalty
Initial $14,063 · Current $14,063

Hazardous substances 8870

29 CFR 1926.960(b)(2): Electric lines and equipment were not considered or treated as energized when they had not been de-energized in accordance with 1926.961.  At a worksite located at 27606 Highway F, Maryville, Missouri.  Employees were exposed to serious electrical shock and burn hazards. Employees who were installing a new service line around energized lines were exposed to live electrical parts which were not treated as energized. Employees were exposed to 7.2 kV of electrical current.
Recent events (2)
  • — I (S) $14063
  • — Z (S) $14063

1926.960 E03

Serious Gravity 10 1 instance 2 exposed
Issued
May 24, 2023
Abate by
Jun 29, 2023
Penalty
Initial $14,063 · Current $0 Reduced

Hazardous substances 8870

29 CFR 1926.960(e)(3): Loose conductors. When lines or equipment are connected to or disconnected from energized circuits, an employee shall keep loose conductors away from exposed energized parts.  At a worksite located at 27606 Highway F, Maryville, Missouri.  Employees were exposed to serious electrical shock and burn hazards. An employee working on a United Electric Power pole # 047760 from an Altec Model AT40G bucket mounted on a 2015 Dodge 550 Vin # 3C7WRNAJ6FG706000, failed to keep loose conductors away from exposed energized parts. A service line that the employees were installing came into contact with an energized power line. Employees were exposed to 7.2 kV of electrical current.
Recent events (2)
  • — I (S) $0
  • — Z (S) $14063

1926.964 B01

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
May 24, 2023
Abate by
Jul 13, 2023
Penalty
Initial $14,063 · Current $0 Reduced

Hazardous substances 8870

29 CFR 1926.964(b)(1): Tension stringing method. When lines that employees are installing or removing can contact energized parts, the employer shall use the tension stringing method, barriers, or other equivalent measures to minimize the possibility that conductors and cables the employees are installing or removing will contact energized power lines or equipment.  At a worksite located at 27606 Highway F, Maryville, Missouri., Employees were exposed to serious electrical shock and burn hazards. Employees who were working from a utility bucket truck on United Electric Power pole # 047760, did not use the tension stringing method, barriers, or other equivalent measures to minimize the possibility of the service line that the employees were working on to contact Ozarks Electric Cooperatives energized power lines. Employees were exposed to 7.2 kV of electrical current.
Recent events (2)
  • — I (S) $0
  • — Z (S) $14063

View United Electric Cooperative's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346386170.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.