On , OSHA opened a complaint safety inspection of SALAMANDER INNISBROOK, LLC. in 1402 INNISBROOK DR, PALM HARBOR, FL 34683 (NAICS 713910). OSHA activity number 346390081.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Salamander Innisbrook, LLC. — free Get an email when a new federal OSHA severe-injury report for Salamander Innisbrook, LLC. is published. One employer, no account, unsubscribe in one click.
Site address
1402 INNISBROOK DR
City
PALM HARBOR
State
FL
ZIP
34683
Mailing
36750 US HWY 19 N, PALM HARBOR, FL 34684
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
713910
Employees
482
Ownership type
A

5 citations on file for this inspection.

1910.303 G01 I A

Serious Gravity 10 2 instances 3 exposed
Issued
Jan 20, 2023
Abate by
Feb 1, 2023
Penalty
Initial $15,625 · Current $9,375 Reduced
29 CFR  1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:  (a) On or about 12/13/2022, at 1402 Innisbrook Dr, Palm Harbor, FL. golf cart parking barn, employees were exposed to electrical shock hazards in that two separate electrical panels were blocked with golf carts in the cart barn.
Recent events (2)
  • — I (S) $9375
  • — Z (S) $15625

1910.303 G02 I D

Serious Gravity 5 2 instances 3 exposed
Issued
Jan 20, 2023
Abate by
Mar 9, 2023
Penalty
Initial $11,162 · Current $6,697 Reduced
29 CFR  1910.303(g)(2)(i)(D): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by elevation of 2.44 m (8.0 ft) or more above the floor or other working surface.  a) On or about 12/13/2022, at 1402 Innisbrook Dr, Palm Harbor, FL. golf cart parking barn, employees were exposed to electrocution hazards in that live exposed wires were approximately 81 inches from the floor.
Recent events (2)
  • — I (S) $6697.2
  • — Z (S) $11162

1910.305 G01 IV A

Serious Gravity 10 4 instances 3 exposed
Issued
Jan 20, 2023
Abate by
Mar 9, 2023
Penalty
Initial $15,625 · Current $9,375 Reduced
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  (a) On or about 12/13/2022, at 1402 Innisbrook Dr, Palm Harbor, FL. golf cart parking barn, employees were exposed to electric shock hazards in that extension cords and power strips had been used as permanent wiring.
Recent events (2)
  • — I (S) $9375
  • — Z (S) $15625

1910.141 A05

Other-than-serious 1 instance 3 exposed
Issued
Jan 20, 2023
Abate by
Feb 15, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.141(a)(5): A continuing and effective extermination program was not instituted where rodents, insects, or other vermin were detected:  (a) On or about 12/13/2022, at 1402 Innisbrook Dr, Palm Harbor, FL. golf cart parking barn, employees were exposed to insect bite hazards, in that the cart barn ceiling was infested with spiders.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 A02 IX

Other-than-serious 1 instance 3 exposed
Issued
Jan 20, 2023
Abate by
Mar 9, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.305(a)(2)(ix):Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard.  (a) On or about 12/13/2022, at 1402 Innisbrook Dr, Palm Harbor, FL. golf cart parking barn, light fixtures were not provided with a cover to prevent breakage and or accidental contact.