TULALIP, WA —
OSHA Inspection: TULALIP RESORT CASINO
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of TULALIP RESORT CASINO in 10200 QUIL CEDA BLVD., TULALIP, WA 98271 (NAICS 721120). OSHA activity number 346397458.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TULALIP RESORT CASINO
- Site address
- 10200 QUIL CEDA BLVD.
- City
- TULALIP
- State
- WA
- ZIP
- 98271
- Mailing
- 10200 QUIL CEDA BLVD., TULALIP, WA 98271
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721120
- Employees
- 600
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.101 B
- Issued
- Mar 13, 2023
- Abate by
- Apr 20, 2023
- Penalty
- Initial $6,831 · Current $4,782 Reduced
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: a) Warehouse HVAC maintenance room, a compressed gas cylinder containing Nitrogen was adjacent to the wall and not properly secured for storage, exposing employees to struck-by hazards.
Recent events (2)
- — I (S) $4781.7
- — Z (S) $6831
1910.178 G02
- Issued
- Mar 13, 2023
- Abate by
- Apr 20, 2023
- Penalty
- Initial $6,831 · Current $0 Reduced
General-duty citation text
29 CFR 1910.178(g)(2): Facilities were not provided with adequate ventilation for dispersal of fumes from gassing batteries. (a) In the facility's main warehouse the employer had a charging area for the electric fork lifts that used lead/acid batteries. Accumulation of Hydrogen and Oxygen gasses can lead to fires and explosions exposing employees to burns and smoke inhalation.
Recent events (2)
- — I (S) $0
- — Z (S) $6831
1910.303 G01 II
- Issued
- Mar 13, 2023
- Abate by
- Apr 20, 2023
- Penalty
- Initial $5,122 · Current $3,585 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: (a) In the facility's food/beverage shipping and receiving loading dock area a 120 Volt Electrical Panel Box (XLALD) was blocked by a stationary storage shelf, clutter, and cleaning materials that would restrict employee access to the panel in an emergency.
Recent events (2)
- — I (S) $3585.4
- — Z (S) $5122
1910.303 B02
- Issued
- Mar 13, 2023
- Abate by
- Apr 20, 2023
- Penalty
- Initial $5,122 · Current $2,561 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) In the Blackfish Grill Kitchen, the employer utilized a pendant cord power supply equipped with a receptacle enclosed in a standard fixture box to power an Alto-Shaam Food warmer cabinet on wheels. The fixture box was not sufficiently durable to be used as part of a pendant box.
Recent events (2)
- — I (O) $2561
- — Z (S) $5122
1910.37 A03
- Issued
- Mar 13, 2023
- Abate by
- Apr 20, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route was not kept free and unobstructed: a) In the Employee Dining Room Kitchen, kitchen push-carts were located within the exit pathway and obstructed the area's labeled emergency exit route.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.157 C01
- Issued
- Mar 13, 2023
- Abate by
- Apr 20, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted so that they were readily accessible without subjecting the employees to possible injuries: (a) On the floor next to the access door connecting the Blackfish Grill prep area and kitchen, there was a fire extinguisher that was not mounted and secured.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Tulalip Resort Casino
View Tulalip Resort Casino's full OSHA safety record →
More inspections in this industry (NAICS 721120)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346397458.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.