WILKES BARRE, PA —
OSHA Inspection: SID HARVEY INDUSTRIES, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of SID HARVEY INDUSTRIES, INC. in 1052 HANOVER STREET, WILKES BARRE, PA 18706 (NAICS 423730). OSHA activity number 346417538.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SID HARVEY INDUSTRIES, INC.
- Site address
- 1052 HANOVER STREET
- City
- WILKES BARRE
- State
- PA
- ZIP
- 18706
- Mailing
- 1052 HANOVER STREET, WILKES BARRE, PA 18706
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423730
- Employees
- 60
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.28 B01 I
- Issued
- Apr 26, 2023
- Abate by
- May 22, 2023
- Penalty
- Initial $7,366 · Current $4,750 Reduced
General-duty citation text
29 CFR 1910.28(b)(1)(i): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling by one or more of the systems described in 29 CFR 1910.28(b)(1)(i): a) Loading Dock: On or about January 4, 2023, employees were exposed to a fall in excess of four (4) feet from the loading dock bays to the lower surface outside the building due to a lack of fall protection such as a guardrail system, safety net system, or personal fall protection system. Abatement certification required.
Recent events (2)
- — I (S) $4750
- — Z (S) $7366
1910.303 B02
- Issued
- Apr 26, 2023
- Penalty
- Initial $9,822 · Current $6,375 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Shipping Area: On or about January 4, 2023, employees were exposed to electrical shock and fire hazards due to relocatable power taps being daisy chained to other relocatable power taps or extension cords while being permanently secured to the desk supports. b) CIS Area: On or about January 4, 2023, employees were exposed to electrical shock and fire hazards due to relocatable power taps being daisy chained to other relocatable power taps or extension cords. c) Parcel Area: On or about January 4, 2023, employees were exposed to electrical shock and fire hazards due to relocatable power taps being attached to the building structure such as desk supports. Note: Under the United Laboratories 2015 White Book the section for Relocatable Power Taps (XBYS) states: "Relocatable power taps are not intended to be permanently secured to building structures, tables, work benches or similar structures, nor are they intended to be used as a substitute for fixed wiring." AND "Relocatable power taps are intended to be directly connected to a permanently installed branch-circuit receptacle outlet. Relocatable power taps are not intended to be series connected (daisy chained) to other relocatable power taps or to extension cords." Abatement certification required.
Recent events (2)
- — I (S) $6375
- — Z (S) $9822
1910.305 G01 IV A
- Issued
- Apr 26, 2023
- Penalty
- Initial $9,822 · Current $6,375 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Maintenance Area: On or about January 4, 2023, employees were exposed to electrical shock hazards due to flexible cords being used as a substitute for fixed wiring. b) Shipping Area: On or about January 4, 2023, employees were exposed to electrical shock hazards due to flexible cords being used as a substitute for fixed wiring. c) CIS Area: On or about January 4, 2023, employees were exposed to electrical shock hazards due to flexible cords being used as a substitute for fixed wiring. d) Parcel Area: On or about January 4, 2023, employees were exposed to electrical shock hazards due to flexible cords being used as a substitute for fixed wiring. Corrected during inspection.
Recent events (2)
- — I (S) $6375
- — Z (S) $9822
1910.305 G01 IV D
- Issued
- Apr 26, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces: a) Maintenance Area: On or about January 4, 2023, employees were exposed to electrical shock hazards due to flexible cords being attached to building surfaces such as overhead light supports and fixed electrical conduit. b) Shipping Area: On or about January 4, 2023, employees were exposed to electrical shock hazards due to flexible cords being attached to building surfaces such as building supports and metal desks. c) CIS Area: On or about January 4, 2023, employees were exposed to electrical shock hazards due to flexible cords being attached to building surfaces such as a shelving unit. d) Parcel Area: On or about January 4, 2023, employees were exposed to electrical shock hazards due to flexible cords being attached to building surfaces such as shelving units and desks. Corrected during inspection.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Apr 26, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) Shipping Area: On or about January 4, 2023, employees were exposed to electrical shock hazards due to flexible cords not having strain relief while performing shipping operations. b) Parcel Area: On or about January 4, 2023, employees were exposed to electrical shock hazards due to flexible cords not having strain relief while performing shipping operations. Corrected during inspection.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at SID Harvey Industries, INC.
View SID Harvey Industries, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 423730)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346417538.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.