MIAMI, FL —
OSHA Inspection: CONCURRENT GROUP LLC
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of CONCURRENT GROUP LLC in SW 107TH AVENUE AND 162ND TERRACE, MIAMI, FL 33157 (NAICS 221122). OSHA activity number 346419914.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CONCURRENT GROUP LLC
- Site address
- SW 107TH AVENUE AND 162ND TERRACE
- City
- MIAMI
- State
- FL
- ZIP
- 33157
- Mailing
- 475 SENTRY PARKWAY E SUITE 200, BLUE BELL, PA 19422
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- Employees
- 4
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.959 D01
- Issued
- Jun 30, 2023
- Abate by
- Jul 20, 2023
- Penalty
- Initial $15,625 · Current $0 Reduced
General-duty citation text
29 CFR 1926.959(d)(1): Mechanical equipment was operated so that the minimum approach distances established under 1926.960(c)(1)(I) were not maintained from exposed energized lines and equipment: On or about 01/04/2023, on a worksite located at the intersection of SW 107th Avenue and 162nd Terrace in Miami, Florida, an employee was exposed to an electrocution hazard when operating a digger derrick truck within the minimum approach distance to energized 7,620-volt overhead power lines while those lines were not insulated.
Recent events (3)
- — J (S) $0
- — C (S) $15625
- — Z (S) $15625
1926.960 C01 III B
- Issued
- Jun 30, 2023
- Abate by
- Jul 20, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.960(c)(1)(iii)(B): The employer did not ensure energized parts were insulated when conductive objects were taken closer that the employers established minimum approach distance: On or about 01/04/2023, on a worksite located at the intersection of SW 107th Avenue and 162nd Terrace in Miami, Florida, an employee was exposed to an electrocution hazard when operating a digger derrick truck within the minimum approach distance to energized 7,620-volt overhead power lines while those lines were not insulated.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1926.959 D02
- Issued
- Jun 30, 2023
- Abate by
- Jul 20, 2023
- Penalty
- Initial $12,656 · Current $0 Reduced
General-duty citation text
29 CFR 1926.959(d)(2): The employer did not ensure that a designated employee other than the equipment operator observed the approach distance to exposed lines and equipment and provide timely warnings before the minimum approach distance required by paragraph (d)(1) of this section was reached: On or about 01/04/2023, on a worksite located at the intersection of SW 107th Avenue and 162nd Terrace in Miami, Florida, an employee was exposed to electrocution hazards when the employer failed to ensure that an observer was designated to observe and warn the employee working near energized and uninsulated 7,620-volt overhead power lines before the minimum approach distance was reached.
Recent events (3)
- — J (S) $0
- — C (S) $12656
- — Z (S) $12656
1926.959 D03 III
- Issued
- Jun 30, 2023
- Abate by
- Jul 20, 2023
- Penalty
- Initial $12,656 · Current $0 Reduced
General-duty citation text
29 CFR 1926.959(d)(3)(iii): The employer did not ensure that each employee was protected from hazards that could arise from mechanical equipment contact with energized lines or equipment by using the best available ground to minimize the time the lines or electric equipment remain energized: On or about 01/04/2023, on a worksite located at the intersection of SW 107th Avenue and 162nd Terrace in Miami, Florida, an employee was exposed to electrocution hazards when the employer did not ensure that grounding of the equipment and insulating protective equipment was utilized before employees began working near an energized and uninsulated 7,620-volt overhead power line.
Recent events (3)
- — J (S) $0
- — C (S) $12656
- — Z (S) $12656
1926.20 B02
- Issued
- Jun 30, 2023
- Abate by
- Jul 20, 2023
- Penalty
- Initial $0 · Current $28,656
General-duty citation text
29 CFR 1926.20(b)(2): The employer did not initiate and maintain programs which provided for frequent and regular inspections of the job site, materials and equipment to be made by a competent person(s) a) On or about 01/04/2023, on a worksite located at the intersection of SW 107th Avenue and 162nd Terrace in Miami, Florida, employees were exposed to electrical hazards when working in close proximity to energized 7,620-volt overhead power lines and the employer had not performed an inspection of the site and equipment to ensure employees did not approach those lines.
Recent events (3)
- — J (S) $28655.9
- — C (S) $0
- — Z (S) $0
More inspections at Concurrent Group LLC
View Concurrent Group LLC's full OSHA safety record →
More inspections in this industry (NAICS 221122)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346419914.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.