FORT WORTH, TX —
OSHA Inspection: JC ELECTRIC, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of JC ELECTRIC, INC. in 6900 BAYBERRY DR., FORT WORTH, TX 76137 (NAICS 238210). OSHA activity number 346428006.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- JC ELECTRIC, INC.
- Site address
- 6900 BAYBERRY DR.
- City
- FORT WORTH
- State
- TX
- ZIP
- 76137
- Mailing
- 12057 KATY ROAD SUITE 205, FORT WORTH, TX 76244
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 30
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.333 A01
- Issued
- Jan 23, 2023
- Abate by
- Feb 21, 2023
- Penalty
- Initial $7,813 · Current $4,688 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee works on or near them. On January 9, 2023, where the MSB main switch panel was not de-energized prior to employees demoing the electrical panel box, exposing the employee(s) to arc flash hazards.
Recent events (2)
- — I (S) $4687.8
- — Z (S) $7813
1910.333 B01
- Issued
- Jan 23, 2023
- Abate by
- Feb 21, 2023
- Penalty
- Initial $4,687 · Current $2,812 Reduced
General-duty citation text
29 CFR 1910.333(b)(1): The employer did not ensure that exposed deenergized parts were locked out and tagged in accordance with paragraph (b) and treated them as energized parts. On January 9, 2023, where employees began working around live parts before energized parts such as the transformer were deenergized and locked out exposing the employees to arc flash burn hazards.
Recent events (2)
- — I (S) $2812.2
- — Z (S) $4687
1910.333 B02 II B
- Issued
- Jan 23, 2023
- Abate by
- Feb 21, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(ii)(B): The circuits and equipment to be worked on were not disconnected from all electric energy sources. On January 9, 2023, the employer did not ensure the MSB panels were disconnected and failed to wait for ONCOR to perform the disconnecting of all energized energy sources before exposing the employees to arc flash burn hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.332 B02
- Issued
- Jan 23, 2023
- Penalty
- Initial $746 · Current $448 Reduced
General-duty citation text
29 CFR 1910.332(b)(2): Employees, who were not qualified persons, were not trained in and familiar with any electrically related safety practices not specifically addressed by 29 CFR 1910.331 through 29 CFR 1910.335, but which were necessary for their safety. On January 9, 2023, and at times prior thereto, the employer did not ensure employees were properly trained to recognize and understand unsafe working conditions when working on or near energized equipment such as but not limited to the MSB main switch panel exposing the employees to arc flash hazards.
Recent events (2)
- — I (O) $447.6
- — Z (O) $746
More inspections at JC Electric, INC.
View JC Electric, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346428006.