Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CADDELL CONSTRUCTION CO. (DE) LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of CADDELL CONSTRUCTION CO. (DE) LLC in 10804 TRI HAMPTON PARKWAY FORT JACKSON, COLUMBIA, SC 29207 (NAICS 236220). OSHA activity number 346438690.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Caddell Construction CO. (DE) LLC — free Get an email when a new federal OSHA severe-injury report for Caddell Construction CO. (DE) LLC is published. One employer, no account, unsubscribe in one click.
Site address
10804 TRI HAMPTON PARKWAY FORT JACKSON
City
COLUMBIA
State
SC
ZIP
29207
Mailing
PO BOX 210099, MONTGOMERY, AL 36121
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
8
Ownership type
A

3 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 1 instance 8 exposed
Issued
Feb 15, 2023
Penalty
Initial $8,539 · Current $5,123 Reduced
29 CFR  1926.403(b)(2):Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:   a) Break room in Job Trailer: A Project Source Relocatable Power Tap Model #0096901 designed and listed to provide power to high concentrations of low powered loads such as computers, printers, radios, etc. was instead used to provide power to high powered loads such as a Mr. Coffee Coffee Maker, a Hamilton Beach Microwave Oven, and a Walmart Toaster Oven.
Recent events (2)
  • — I (S) $5123.4
  • — Z (S) $8539

1926.404 B02

Deleted Serious Gravity 5 1 instance 8 exposed
Issued
Feb 15, 2023
Penalty
Initial $0 · Current $0
29 CFR  1926.404(b)(2): Outlet devices had an ampere rating  less than the load to be served:   a) Break room in Job Trailer: A Project Source Relocatable Power Tap Model #0096901 designed and listed to provide power to  a Mr. Coffee Coffee Maker (9.16 amps), a Hamilton Beach Microwave Oven (11.25 amps), and a Walmart Toaster Oven (8.3 amps) with a total of 28.71 amps, was larger than the relocatable power taps' 15 amp limit.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 G01 III B

Deleted Serious Gravity 5 2 instances 8 exposed
Issued
Feb 15, 2023
Penalty
Initial $0 · Current $0
29 CFR  1926.405(g)(1)(iii)(B): 29 CFR 1926.405(g)(1)(iii)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:  a) Copy room area in Job Trailer: A Project Source Relocatable Power Tap Model #0096901 ran through a hole cut into the wall and was plugged into a receptacle located in the Break Room behind it. It was used to power the copy machine and other low power electrical equipment.   b) Conference Room in the Job Trailer: two 120 volt construction grade extension cords  ran through a hole cut into the wall and were used to provide electrical power to office equipment in the reception area located behind the wall.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Caddell Construction CO. (DE) LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346438690.