Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: KL MANUFACTURING, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of KL MANUFACTURING, LLC in 1004 E CENTRAL AVE, CENTRAL CITY, AR 72941 (NAICS 336214). OSHA activity number 346445703.

Watch KL Manufacturing, LLC — free Get an email when a new federal OSHA severe-injury report for KL Manufacturing, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1004 E CENTRAL AVE
City
CENTRAL CITY
State
AR
ZIP
72941
Mailing
PO BOX 518, LAVACA, AR 72941
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336214
Employees
3
Ownership type
A

7 citations on file for this inspection.

1910.253 B04 III

Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $2679.00 · Current $1340.00 Reduced
29 CFR  1910.253(b)(4)(iii):  Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least:  a) On or about January 19, 2023, in the welding shop, employees were engaged in work activities related to the manufacture of  trailers where oxygen cylinders were stored within 20 feet of propane tanks and acetylene cylinders.
Recent events (2)
  • — I (S) $1339.5
  • — Z (S) $2679

1910.303 B01

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $4688.00 · Current $2344.00 Reduced
29 CFR  1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:   On or about January 19, 2023, throughout the facility, employees were engaged in work activities related to manufacturing activities were exposed to electrical deficiencies, such as, but not limited to the following:  (a) Flexible cords and cables were used in lieu of permanent wiring where run through holes in electrical panels and switch enclosures that were not protected from damage; (b) Conduit fittings where  conductors enter panels were not secured; (c) Junction box hanging from flexible conduit running over a refrigerator; (d)  An open junction box was mounted to the metal frame between the transformer and the panel that was missing its cover; (e) Live electrical parts over 50-V were not guarded.
Recent events (2)
  • — I (S) $2344
  • — Z (S) $4688

1910.333 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4688.00 · Current $2344.00 Reduced
29 CFR  1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:   a) On or about January 17, 2023, in the welding shop, employees were performing electrical rewiring in electrical panels without deenergizing them before starting the electrical work.
Recent events (2)
  • — I (S) $2344
  • — Z (S) $4688

1910.333 C02

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4688.00 · Current $2344.00 Reduced
29 CFR  1910.333(c)(2): The employer did not ensure that only qualified persons were working on energized circuits and that qualified persons were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools:  a) On or about January 17, 2023, in the welding shop, employees were performing electrical rewiring without being trained in electrical safety-related work practices.
Recent events (2)
  • — I (S) $2344
  • — Z (S) $4688

1910.335 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $4688.00 · Current $0.00 Reduced
29 CFR  1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  a) On or about January 17, 2023,  in the welding shop, employees were performing electrical work on live equipment in excess of 50-V while wearing only safety glasses.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4688

1904.39 A02

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3349.00 · Current $3349.00
29 CFR  1904.39(a)(2):  The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye:  a) On or about January 17, 2023 in the welding shop an employee performing electrical work received a work related injury resulting inpatient hospitalization.  The employer did not report the incident to OSHA.
Recent events (2)
  • — I (O) $3349
  • — Z (O) $3349

1910.22 A01

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.22(a)(1):  The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition:   On or about January 19, 2023,  in the welding shop, employees were performing work activities related to manufacturing of utility trailers were exposed to the following: (a)  Along the western wall, metal dust and shavings accumulated on the floor and electrical wiring; (b) In the northwestern corner, debris including metal screws accumulated on the floor; (c) On the southern side, near the entrance, buckets of parts and equipment were stored on the floor; (d) On the southern side, near the entrance, material being stored was not orderly.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346445703.